Permit Information
Permit NumberFIR03-00487
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 5493 E WARM SPRINGS AVE
Project NamealmRiverstone Community School
Customer Number 
ePlanReview 
Description
Required manual fire alarm system in a new modular classroom building. The new system consists of manual pull stations, smoke detection and notification appliances.

The associated building permit (BLD 03-01716) is to install footings, landings, covered entrance and walkway and roof structure on a 11,808 sq. ft. multi-unit modular classroom building. Other work includes site improvements , paving and landscaping. All work is per approved plans and attachments. DRH03-00031 CUP99-00011/MOD #3. All units are to have State of Idaho Tags - State Plan Approval # 12032FB, Tag #'s 9397FB, units A-O. Riverstone Community School *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/5/20042/5/20042/5/2004PPASS
DetailsRick Jackson
all items corrected; smoke/firedampers installed and operated with alarm condition 2/5/2004 2:48:51 PM
DOC - Permit Finaled2/5/20042/5/20042/5/2004PPASS
DetailsRick Jackson
Finaled by inspector at 2/5/2004 2:48:56 PM
INSP-Final Inspection12/4/200312/4/200312/4/2003PPART
DetailsRick Jackson
need resubmittals for relays to control 4 smoke/fire dampers
INSP-Final Inspection11/26/200311/26/200311/26/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 11/26/2003 at 8:59:41 AM. Contact: ###-####. need to relocate smoke detector away from diffuser at FACP; need map of initiating devices; record of completion when complete 11/26/2003 4:31:24 PM
Issue and Print Permit  9/18/2003 DONE
Plan resubmittals received  9/17/2003 DONE
Received revised battery calculations.
Alarm Plan Check  9/17/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/17/2003 DONE
Inspection Record Card- Fire9/17/2003 9/17/2003 DONE
Permit Ready to Issue  9/17/2003 DONE
Telephone call  9/17/2003 DONE
permit ready and fees due
Telephone call  9/16/2003 DONE
Called Synergy to get clarification on the battery calculations. Spoke with Nick, he stated he would double check the calculations and fax over a revised calc by Thursday, 9/18.
Miscellaneous action  9/3/2003  
Waiting for building permit (BLD03-01716) to be approved. Fire alarm plans on hold.
Application received  8/22/2003  
Plan assigned to (SAM)8/22/2003