Permit Information
Permit NumberFIR03-00500
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 10790 W FRANKLIN RD
Project Namealm - IDAHO POWER BOC
Customer Number 
ePlanReview 
Description
Add five (5) duct smoke detectors to an existing fire alarm system for HVAC shutdown.

There is no associated building permit.
The associated mechanical permit. (MEC 03-02144) is to install 5-heat pump package units, ductwork, t-stats, curbs.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/25/200312/2/200312/2/2003PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 11/25/2003 at 12:13:22 PM. Contact: ###-####. 17.2 amp hr batteries are installed, not the 18 amp hr shown on plans and 10 amp hr are required per plans; two additional RTU's will be installed in the future; address 12-16 were used instead of 5-8 12/2/2003 2:00:47 PM
DOC - Permit Finaled12/2/200312/2/200312/2/2003PPASS
DetailsRick Jackson
Finaled by inspector at 12/2/2003 2:00:53 PM
Permit Ready to Issue  10/30/2003 DONE
Inspection Record Card- Fire10/30/2003 10/30/2003 DONE
Telephone call  10/30/2003 DONE
Spoke with Peter told permit ready & fees
Issue and Print Permit  10/30/2003 DONE
Plan assigned to (SAM)8/27/2003 10/29/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/29/2003 DONE
Alarm Plan Check  10/29/2003 PASS
Approved pending field inspection of fire alarm permit comments.
Plan resubmittals received  10/20/2003 DONE
Alarm Plan Check  9/10/2003 FAIL
Resubmittal required. Faxed comments to Peter Petroni 9/10/2003.
Telephone call  9/9/2003  
Left a message for Peter Petroni regarding the functionality of the duct detectors to "alarm" the panel. IFC 2000 states it should be a supervisory signal. Peter is out of the office until tomorrow.
Application received  8/27/2003