Permit Information
Permit NumberFIR03-00505
StatusFinaled
Name AIC SOLUTIONS INC
Site Address 6711 W NORTHVIEW ST
Project Namealm- Northview LDS Church
Customer Number 
ePlanReview 
Description
To provide a new fire alarm system, manual pull stations, fire/smoke damper functions, HVAC shutdown, door release service and notification appliances.

The associated building permit (BLD 03-02743) is to remodel existing church and infill an existing 832 sq. ft. court yard and add 136 sq. ft. of architectural walls to the north side. Other work includes with new trash enclosure and some minor landscaping and site work. All work per approved plans and attachments (Addition and Remodel)- CUP02-00097
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled1/29/20041/29/20041/29/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 1/29/2004 7:56:01 AM
INSP-Final Inspection1/29/20041/29/20041/29/2004APASS
DetailsTroy Cobbley
INSP-Final Inspection1/26/20041/27/20041/27/2004PFAIL
DetailsTroy Cobbley
provide knox box, provide map at the annunciator and label the zones at the annunciator 1/27/2004 1:52:28 PM
INSP-Final Inspection1/20/20041/21/20041/21/2004PCANC
DetailsTroy Cobbley
phone lines not in 1/21/2004 4:05:54 PM
INSP-Final Inspection1/20/20041/20/20041/20/2004PCANC
DetailsTroy Cobbley
phone lines are not in yet 1/20/2004 2:57:42 PM
INSP-Conference1/12/20041/12/20041/12/2004PDONE
DetailsTroy Cobbley
I issued a citation to bill ramsey with Benchmark Electric for beginning instalation of the fire alarm system prior to having approved plans
Inspection Record Card- Fire11/12/2003 11/12/2003 DONE
Permit Ready to Issue  11/12/2003  
Telephone call  11/12/2003 DONE
left mess that permit is ready
Issue and Print Permit  11/12/2003  
PLANS/APPL TAKEN TO FRONT DESK  11/10/2003 DONE
Alarm Plan Check  11/10/2003 PASS
Approved pending field inspection of fire alarm permit comments.
Plan assigned to (SAM)8/28/2003 11/10/2003 DONE
INSP-Conference11/7/200311/7/200311/7/2003ADONE
DetailsTroy Cobbley
I stopped by the project per Mary's request and found that Don Lustig of BenchMark Electric, ###-####, has begun installing conduit, flex, wiremold, backboxes and wire for the fire alarm system. I issued a stop work order, placed it on exterior door, for the installation of the fire alarm system until fire alarm plans have been issued. The electrician stated that AIC told him they were given permission by the city to begin installation. I told him I would verify that on monday. I sent a follow up email to Mary
Plan resubmittals received  11/6/2003 DONE
Received updated riser and cut sheets for the ceiling mounted appliances.
Telephone call  11/5/2003 DONE
Spoke with Qunicy. Explained that I noticed a flow switch, tamper switch and a PIV on the riser diagram. The building is not sprinklered. I requested an updated riser and stated that I would complete my review when I received the riser and cut sheets for a ceiling mount A/V devices.
Telephone call  10/28/2003 DONE
Brian called to state the A/V appliances in rooms 145 through 147 have been placed on the cabinets, not in the ceiling. (The ceiling is an existing "hard-lid", installers are afraid of damaging and having to replace the entire ceiling). I told him that the A/V devices on the walls in 148 and 145 may help the "dead" areas at the doorways. He also asked where to place the smoke detector for the smoke door in the cultural center. I explained that that was an engineering item (I had a conversation with the design engineer regarding this door already) and he should have him locate it.
Plan resubmittals received  10/24/2003 DONE
Alarm Plan Check  9/9/2003 FAIL
Resubmittal required. Faxed comments to Marty Wolford 9/9/2003.
Application received  8/28/2003