Permit NumberFIR03-00507
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1055 N CURTIS RD
Project Namealm - ST ALS-NORTH TOWER
Customer Number 
ePlanReview 
Description
Remove existing chimes/strobes. Add to an existing fire alarm system, notification devices in the library area and corridor and two (2) duct detectors to HVAC units that feed the library.

The associated building permit (BLD 03-00979) is to remodel a 2,654 sq.ft. area in the basement to convert space from mechanical/storage to a library and office per approved plans on file. NOTE: This building is fully sprinklered with alarm system. A "Letter of Compliance is required for this project. (SAINT ALPHONSUS LIBRARY)(CURTIS PROFESSIONAL PLAZA-BASEMENT) PC03-240/drs

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/28/200310/28/200310/28/2003PPASS
DetailsTroy Cobbley
brian; Phone #: ###-#### Internet Inspection Request from: Annette Moore
DOC - Permit Finaled10/28/200310/28/200310/28/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 10/28/2003 3:39:50 PM
INSP-Final Inspection10/21/200310/27/200310/27/2003ACANC
DetailsTroy Cobbley
This inspection was cancelled due to problems with central station communications. all devices tested ok but there is a problem with the ADT Focus dialer. To sent a signal to the central station it appears a person has to manually push the reset button each time a signal comes comes into the panel. Alarm signals are not getting to central station within the 90 seconds allowed by coded and may not even get there unless that button gets pushed. 10/27/2003 10:11:05 AM
Issue and Print Permit  9/24/2003 DONE
Inspection Record Card- Fire9/23/2003 9/23/2003 DONE
Permit Ready to Issue  9/23/2003 DONE
Telephone call  9/23/2003 DONE
permit ready and fees due
Alarm Plan Check  9/22/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/22/2003 DONE
Plan assigned to (SAM)8/29/2003 9/22/2003 PASS
Plan resubmittals received  9/15/2003  
Application received  8/29/2003  
Alarm Plan Check9/10/2003   FAIL
Resubmittal required. Faxed comments to Paul Highley 9/10/2003.