INSP-Final Inspection | 10/28/2003 | 10/28/2003 | 10/28/2003 | P | PASS |
Troy Cobbley
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
DOC - Permit Finaled | 10/28/2003 | 10/28/2003 | 10/28/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/28/2003 3:39:50 PM
|
INSP-Final Inspection | 10/21/2003 | 10/27/2003 | 10/27/2003 | A | CANC |
Troy Cobbley
|
|
|
This inspection was cancelled due to problems with central station communications. all devices tested ok but there is a problem with the ADT Focus dialer. To sent a signal to the central station it appears a person has to manually push the reset button each time a signal comes comes into the panel. Alarm signals are not getting to central station within the 90 seconds allowed by coded and may not even get there unless that button gets pushed. 10/27/2003 10:11:05 AM
|
Issue and Print Permit | | | 9/24/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2003 | | 9/23/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2003 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2003 | | DONE |
|
|
|
permit ready and fees due
|
Alarm Plan Check | | | 9/22/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 8/29/2003 | | 9/22/2003 | | PASS |
|
|
|
|
Plan resubmittals received | | | 9/15/2003 | | |
|
|
|
|
Application received | | | 8/29/2003 | | |
|
|
|
|
Alarm Plan Check | 9/10/2003 | | | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Paul Highley 9/10/2003.
|