INSP-Final Inspection | 1/8/2004 | 1/9/2004 | 1/9/2004 | A | CANC |
Troy Cobbley
|
|
|
duplicate inspection 1/9/2004 10:49:13 AM
|
INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 | A | PASS |
Troy Cobbley
|
|
|
fire sprinklers finaled
|
DOC - Permit Finaled | 1/9/2004 | 1/9/2004 | 1/9/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 1/9/2004 10:45:59 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/10/2003 | 10/13/2003 | 10/13/2003 | A | PASS |
Rick Jackson
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Annette Moore okay to cover; insulation is in the space under the fireplace and head installed in concealed space around fireplace; draft stops okay; will need to test alarms and forward flow BFP; as-builts needed 10/13/2003 8:55:21 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/10/2003 | 10/10/2003 | 10/10/2003 | P | FAIL |
Rick Jackson
|
|
|
ERIC; Phone #: ###-#### Internet Inspection Request from: Annette Moore combustible cavity around/under fireplace requires protection or make it noncombustible; draft stop penetrations; insulation on heads in attic area; minor changes made to rooms on east side to prevent overspacing; hydro on overhead okay 10/10/2003 12:26:39 PM
|
Plan assigned to (Bill) | 9/11/2003 | | 10/8/2003 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 10/8/2003 | | 10/8/2003 | | PASS |
Bill Alexander
|
|
|
Plans approved with comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/8/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 10/8/2003 | | 10/8/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/8/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/8/2003 | | DONE |
|
|
|
Spoke with Gerald told permit ready & fees
|
Issue and Print Permit | | | 10/8/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/24/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/23/2003 | | 9/23/2003 | | FAIL |
Bill Alexander
|
|
|
Plans denied. Review comments faxed to contractor.
|
Application received | | | 9/11/2003 | | |
|
|
|
|