Permit Information
Permit NumberFIR03-00532
StatusFinaled
Name ALARMCO
Site Address 1405 N MILWAUKEE ST
Project Namealm - T.J. MAXX PLAZA
Customer Number 
ePlanReview 
Description
To provide a new fire alarm system for sprinkler monitoring and HVAC shutdown to an existing structure.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/200311/18/200311/18/2003APASS
DetailsTroy Cobbley
Please notify Warner for time of inspection.; Phone #: ###-#### Internet Inspection Request from: Teresa Costello
DOC - Permit Finaled11/18/200311/18/200311/18/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 11/18/2003 11:00:32 AM
INSP-Final Inspection11/14/200311/17/200311/17/2003AFAIL
DetailsTroy Cobbley
contractor did not have keys to riser room 11/17/2003 9:59:18 AM
INSP-Final Inspection11/10/200311/14/200311/14/2003PFAIL
DetailsTroy Cobbley
Duct smoke detectors in blockbuster video need to be retested since the wrong address came in at the monitoring service. All other items are ok. 11/14/2003 2:07:11 PM
Inspection Record Card- Fire11/6/2003 11/6/2003 DONE
Permit Ready to Issue  11/6/2003 DONE
Telephone call  11/6/2003 DONE
Spoke with Theresa told permit ready & fees
Issue and Print Permit  11/6/2003 DONE
Alarm Plan Check  11/5/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/5/2003 DONE
Plan resubmittals received  10/24/2003 DONE
INSP-Final Inspection10/17/200310/22/200310/22/2003PFAIL
DetailsTroy Cobbley
Provide tamper switch on the anti-freeze system control vavle, provide correct orfice on the sprinkler inspectors test vavles and test flow switches, test duct detectors in 1405,1447 since units would not turn on, test duct detector in 1421 again since central station did not have an address listed, test all remaining duct detectors beyond 1513. Phone lines, batteries, tamper switches and duct detectors up to 1513 that are not listed above are ok. 10/22/2003 2:51:03 PM
Issue permit  10/16/2003  
Inspection Record Card- Fire10/15/2003 10/15/2003 DONE
Permit Ready to Issue  10/15/2003 DONE
Telephone call  10/15/2003 DONE
Spoke with Alan told permit ready & fees
Plan assigned to (SAM)10/1/2003 10/14/2003 DONE
Alarm Plan Check  10/14/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/14/2003 DONE
Plan resubmittals received  10/1/2003 DONE
Issue and Print Permit  9/24/2003 DONE
Plan assigned to (SAM)9/12/2003 9/23/2003  
Alarm Plan Check  9/23/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/23/2003 DONE
Inspection Record Card- Fire9/23/2003 9/23/2003 DONE
Permit Ready to Issue  9/23/2003 DONE
Telephone call  9/23/2003 DONE
permit ready and fees due
Application received  9/12/2003