Permit Information
Permit NumberFIR03-00538
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2201 E PARKCENTER BLVD
Project NameSPR Gold's Gym @ Parkcenter
Customer Number 
ePlanReview 
Description
Gold's Gym at Parkcenter (Shell Building) - To install a complete NFPA 13 (overhead) fire sprinkler system in a new 46,435-ft/2, two story building for "Gold's" gym and exercise facility. This is a shell and T.I. sprinkler permit. (First Floor 31,790-ft/2, second Floor 14,645-ft/2). This building is constructed of concrete tilt-up exterior walls and glazed curtain walls with steel joists and metal pan and concrete floors and metal roof deck. This building is fully fire sprinklered for area increase. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire sprinkler supply work permit is under FIR03-00495. This permit is attached to building permit: BLD03-00538.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/2/20044/2/20044/2/2004PPASS
DetailsRick Jackson
DOC - Permit Finaled4/2/20044/2/20044/2/2004PPASS
DetailsRick Jackson
Finaled by inspector at 4/2/2004 4:39:50 PM
INSP-Sprinkler Rough-in/Hydro3/29/20043/29/20043/29/2004PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 3/29/2004 at 6:53:06 AM. Contact: ###-####. tape on heads - can't verify head type 3/29/2004 2:55:07 PM
INSP-Final Inspection3/5/20043/5/20043/8/2004PPART
DetailsRick Jackson
mike; Phone #: ###-#### Internet Inspection Request from: Darla Downs Phase I complete; will need to verify tanning area of Phase II when this area is completed 3/8/2004 9:53:44 AM
INSP-Final Inspection3/1/20043/1/20043/1/2004PPART
DetailsRick Jackson
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie overhead hydro okay only; need to test tampers/alarms/flow and forward flow BFP 3/1/2004 5:59:31 PM
INSP-Supply line flush2/23/20042/24/20042/24/2004APASS
DetailsRick Jackson
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see UG permit; flush okay - still needs hydro 2/24/2004 8:16:40 AM
INSP-Sprinkler Rough-in2/24/20042/24/20042/24/2004PFAIL
DetailsRick Jackson
heads not installed in two areas; painted heads and heads with tape; SE area, elevator pit, electrical room not completed; no access to SW area; see plans for the above 2/24/2004 2:15:23 PM
Issue and Print Permit  2/17/2004 DONE
Inspection Record Card- Fire2/17/2004 2/17/2004 DONE
Sprinkler Plan Check1/28/2004 2/13/2004 PASS
DetailsBill Alexander
Major building plan modifications to original design on sheet FP-2 (requiring a most demanding remote recalculation/verification).
Plan assigned to (Bill)1/28/2004 2/13/2004 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/13/2004 DONE
Permit Ready to Issue  2/13/2004 DONE
Telephone call  2/13/2004 DONE
CALLED GREG PERMIT READY & FEE GIVEN ///DLD 2-13-04 8:29
Plan resubmittals received  1/28/2004 DONE
INSP-Sprinkler Rough-in11/13/200311/14/200311/14/2003PPART
DetailsRick Jackson
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes womens showers and east side high bay okay 11/14/2003 4:14:28 PM
INSP-Sprinkler Rough-in10/28/200310/28/200310/28/2003PPART
DetailsRick Jackson
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover hard lid areas in first floor restroom; need architect verification for hanging off bottom cord of truss; need data submittal for verfication of unistrut size for 3 inch main on bottom cord - provide for field use 10/28/2003 4:07:36 PM
Plan assigned to (Bill)9/15/2003 9/25/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check9/25/2003 9/25/2003 PASS
DetailsBill Alexander
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  9/25/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire9/25/2003 9/25/2003 DONE
Permit Ready to Issue  9/25/2003 DONE
Telephone call  9/25/2003 DONE
permit ready and fees due
Issue and Print Permit  9/25/2003 DONE
Application received  9/15/2003