Permit Information
Permit NumberFIR03-00541
StatusExpired
Name TREASURE VALLEY FIRE PROTECTION
Site Address 370 S 8TH ST
Project NameSPR 8th St. Market T.l Remodel
Customer Number 
ePlanReview 
Description
The existing space to the east will have all new ceiling fixtures and will require the existing sprinkler system above the ceiling to be abandoned. A new exposed piping system will be added, new 2" super flow piping will replace the schedule 40 piping, and new quick response upright sprinkler heads will replace the pendant sprinkler heads that are being removed. This area will be fed from the existing 3" main via a mechanical tee. This main will be cut and capped at the now exterior wall. The existing space to the west will remain as is except the existing standard response sprinklers will be replaced with new quick response pendant sprinklers. These heads will be fed from the existing 3" main via a mechanical tee supplying 2" super flow pipe.
These changes are required to be made due to the removal of the north end of the building. This demolition of the building has caused the sprinkler piping feeding these two areas to be outside and exposed to the elements.
The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is NOT attached to any other permit.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Expired5/10/20105/10/20105/10/2010PPASS
DetailsForrest France
FIR-Aging Inspection5/10/20105/10/20105/10/2010 DONE
DetailsForrest France
Miscellaneous action  3/12/2010 DONE
Sent email requesting project status.
FIR-Aging Inspection12/31/200312/31/200312/31/2003 NR
DetailsRick Jackson
talked to Jeff Anderson and he will get with George about getting the inspections 12/31/2003 9:14:21 AM
Issue and Print Permit  9/23/2003 DONE
Plan assigned to (Bill)9/16/2003 9/22/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check9/22/2003 9/22/2003 PASS
DetailsBill Alexander
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  9/22/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire9/22/2003 9/22/2003 DONE
Telephone call  9/22/2003  
called left message with julie permit ready & fee given
Application received  9/16/2003