Permit Information
Permit NumberFIR03-00555
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 111 N CLOVERDALE RD
Project NameSPR Fed Ex Freight
Customer Number 
ePlanReview 
Description
Fed Ex Freight Shop Building * To provide a new fire sprinkler system throughout a new 10,600-ft/2, one story with mezzanine truck maintenance shop. This shop building will contain a truck wash, truck inspection area and maintenance shop, as well as, storage and small accessory office area. Main floor area: 9450-ft/2, Mezzanine area: 1150-ft/2. This building is fully fire sprinklered. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-01206.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/24/200311/24/200311/24/2003APASS
DetailsTroy Cobbley
DOC - Permit Finaled11/24/200311/24/200311/24/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 11/24/2003 11:18:34 AM
INSP-Sprinkler Rough-in/Hydro11/20/200311/20/200311/20/2003PPASS
DetailsTroy Cobbley
overhead hydro test is ok. Anti-freeze system hydro test is ok 11/20/2003 3:46:12 PM
INSP-Sprinkler Rough-in/Hydro11/14/200311/14/200311/14/2003PPASS
DetailsTroy Cobbley
Underground hydro is OK
Permit Ready to Issue  11/14/2003 DONE
Telephone call  11/14/2003 DONE
Spoke with Gerald and told permit is ready & fees
Plan assigned to (Bill)11/10/2003 11/13/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check11/10/2003 11/13/2003 PASS
DetailsBill Alexander
Faxed calculations and 8.5 x 11 plan sheet to verify revised spacing installed which exceeds original approved designed.

11/12/03 - Requested calc cover sheet (by email).
11/13/03 - Received calc cover sheet (by fax).
PLANS/APPL TAKEN TO FRONT DESK  11/13/2003 DONE
Miscellaneous action  11/12/2003 DONE
Emailed Gerald Ebeling (12:05 pm), for a revised Fire Sprinkler Cover Sheet, which matches the same calculations provided.
INSP-Supply line flush11/7/200311/10/200311/10/2003APASS
DetailsTroy Cobbley
underground flush is ok 11/10/2003 9:13:09 AM
INSP-Sprinkler Rough-in/Hydro11/7/200311/10/200311/10/2003AFAIL
DetailsTroy Cobbley
Measuring off of wall in anti-freeze area the upright sprinkler heads are over spaced, closet is missing sprinkler protection 11/10/2003 9:11:59 AM
Plan resubmittals received  11/10/2003  
DetailsBill Alexander
INSP-Supply line flush10/9/200310/10/200310/10/2003ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/9/2003 at 12:42:30 PM. Contact: ###-####. see fir03-00376 10/10/2003 9:18:45 AM
Issue and Print Permit  10/3/2003 DONE
Plan assigned to (Bill)9/18/2003 10/2/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check10/2/2003 10/2/2003 PASS
DetailsBill Alexander
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  10/2/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire10/2/2003 10/2/2003 DONE
Inspection Record Card- Fire10/2/2003 10/2/2003 DONE
Permit Ready to Issue  10/2/2003  
Telephone call  10/2/2003 DONE
left mess that permit is ready
Application received  9/18/2003