Permit Information
Permit NumberFIR03-00563
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 8172 W OVERLAND RD
Project NameSPR Venture Development Group
Customer Number 
ePlanReview 
Description
Venture Development Group Retail Shell Building - To install a complete over head fire sprinkler system in a new 18,154-ft/2, one story type VB structure. Separate fire protection plans and fire permits must be obtained for each tenant space in the building. This structure is a fully fire sprinklered retail shell building. Fire sprinklers are used for area increase. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was installed under FIR03-00474. This permit is attached to building permit: BLD03-000706.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/8/200312/9/200312/9/2003APASS
DetailsTroy Cobbley
Bruce --- shell and core, please call first for access.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
DOC - Permit Finaled12/9/200312/9/200312/9/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 12/9/2003 3:20:13 PM
INSP-Sprinkler Rough-in/Hydro12/4/200312/4/200312/4/2003PPART
DetailsRick Jackson
bruce -call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie overhead hydro okay; will additional hangers in video store area; will need to inspect the rest of the building 12/4/2003 5:11:37 PM
Inspection Record Card- Fire12/4/2003 12/4/2003 DONE
Issue and Print Permit  12/4/2003 DONE
Miscellaneous action  12/3/2003 DONE
Received 2 plans (redplacing soiled) plans.
PLANS/APPL TAKEN TO FRONT DESK  12/3/2003 DONE
DetailsBill Alexander
Plan assigned to (Bill)12/2/2003 12/3/2003 DONE
Sprinkler Plan Check12/2/2003 12/3/2003 PASS
DetailsBill Alexander
INSP-Sprinkler Rough-in/Hydro12/2/200312/2/200312/2/2003AFAIL
DetailsTroy Cobbley
two heads of of 1" outlet in address 8170, 8172 and 8176. No pendant in restroom and upright overspaced near restroom in address 8174. Upright overspaced along east wall in address 8184. Plans show 1 1/4" branchlines and 2" far main. 1 1/2" branchlines and 3" far main is installed. Calcs show Dyna Flow pipe but Sch. 40 is installed. Resubmit plans with everything corrected. No other items inspected. Underground flush failed. Hydro test failed on the overhead system. Hydro test passed on canopy system
Plan resubmittals received  12/2/2003 DONE
Miscellaneous action  12/2/2003 DONE
Faxed letter indicating 2 sets are soiled and require resubmitting.
Plan resubmittals received  12/2/2003 DONE
in good cond///dld
INSP-Sprinkler Rough-in11/12/200311/12/200311/12/2003APART
DetailsRick Jackson
okay to cover canopy; 200 degree heads installed for this cavity
Inspection Record Card- Fire10/22/2003 10/22/2003 DONE
Permit Ready to Issue  10/22/2003 DONE
Telephone call  10/22/2003 DONE
Spoke with John told permit ready & fees
Issue and Print Permit  10/22/2003 DONE
Plan assigned to (Bill)9/23/2003 10/21/2003 DONE
Sprinkler Plan Check10/17/2003 10/21/2003 PASS
DetailsBill Alexander
Need data submittals (mising) attached to site plans. Reference review notes.
PLANS/APPL TAKEN TO FRONT DESK  10/21/2003 DONE
Miscellaneous action  10/21/2003 DONE
Emailed copy of review notes to John Warnick: 3:00pm.
Plan resubmittals received  10/17/2003 DONE
Sprinkler Plan Check10/8/2003 10/8/2003 TEMP
DetailsBill Alexander
Plans failed. Review notes faxed to contractor.
Telephone call  10/8/2003 DONE
left mess that permit is ready
Application received  9/23/2003