INSP-Alarm Testing | 3/15/2004 | 3/15/2004 | 3/15/2004 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 3/15/2004 4:20:58 PM
|
DOC - Permit Finaled | 3/15/2004 | 3/15/2004 | 3/15/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/15/2004 4:21:02 PM
|
INSP-Alarm Testing | 3/11/2004 | 3/12/2004 | 3/12/2004 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was set up for 8:15 and the contractor did not show up. I called and left him a message that I was here. 3/12/2004 8:29:53 AM
|
INSP-Final Inspection | 3/1/2004 | 3/1/2004 | 3/1/2004 | P | FAIL |
Troy Cobbley
|
|
|
Door release button does not unlock the door for the minimum 30 seconds. Still need to do the battery calcs 3/1/2004 5:48:16 PM
|
Issue and Print Permit | | | 2/18/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2004 | | DONE |
|
|
|
Left message for Jack that permit is ready & fees//2/17/04 2:48pm BAM
|
Alarm Plan Check | | | 1/28/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/28/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/28/2004 | | 1/28/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/28/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/28/2004 | | DONE |
|
|
|
Left message for Jack that permit is ready & fees//1/28/04 11:54am BAM
|
Plan resubmittals received | | | 1/15/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given until the fire alarm plans have been resubmitted showing the access control connected to the fire alarm. All other fire alarm devices have been tested
|
INSP-Alarm Testing | 1/7/2004 | 1/8/2004 | 1/8/2004 | A | FAIL |
Troy Cobbley
|
|
|
test phone lines, test batteries , submit plans showing the access control, provide alarm signal verification 1/8/2004 11:28:30 AM
|
Issue and Print Permit | | | 11/12/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/6/2003 | | 11/6/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/6/2003 | | DONE |
|
|
|
|
Telephone call | | | 11/6/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Alarm Plan Check | | | 11/5/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Miscellaneous action | | | 11/5/2003 | | |
|
|
|
E-mail from Rick Jackson to Troy Cobbley on 10/8/2003 that he stopped at the site and found four wires from teh sproinkler riser to the east side lobby area. No devices were installed, but the wiring was for fire alarm.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/5/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 9/25/2003 | | 11/5/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/28/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/8/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jack Schmidt 10/8/2003.
|
Application received | | | 9/25/2003 | | |
|
|
|
|