Permit Information
Permit NumberFIR03-00569
StatusFinaled
Name ALARM SYSTEMS INTEGRATION INC
Site Address 6305 W OVERLAND RD
Project Namealm - Interchange Sub #1
Customer Number 
ePlanReview 
Description
To install a required sprinkler monitoring fire alarm system, (11/5/2003) that includes HVAC shutdown and a remote annunciator at the front door. (1/28/2004) - Revised scope to include an access controlled egress front door. The fire alarm system shall deactivate the door upon alarm.

The associated building permit (BLD 03-01107) is to construct a new 7100 sq. ft., one story, wood framed office building and related site improvements. This building will be fully fire sprinklered. All construction per the approved plans and attached comment list. DRH03-00035, CUP03-00014, PC#277-03/JCM Pacific Republic Mortgage*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing3/15/20043/15/20043/15/2004PPASS
DetailsTroy Cobbley
fire alarm finaled 3/15/2004 4:20:58 PM
DOC - Permit Finaled3/15/20043/15/20043/15/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/15/2004 4:21:02 PM
INSP-Alarm Testing3/11/20043/12/20043/12/2004AFAIL
DetailsTroy Cobbley
Inspection was set up for 8:15 and the contractor did not show up. I called and left him a message that I was here. 3/12/2004 8:29:53 AM
INSP-Final Inspection3/1/20043/1/20043/1/2004PFAIL
DetailsTroy Cobbley
Door release button does not unlock the door for the minimum 30 seconds. Still need to do the battery calcs 3/1/2004 5:48:16 PM
Issue and Print Permit  2/18/2004 DONE
Telephone call  2/17/2004 DONE
Left message for Jack that permit is ready & fees//2/17/04 2:48pm BAM
Alarm Plan Check  1/28/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/28/2004 DONE
Inspection Record Card- Fire1/28/2004 1/28/2004 DONE
Permit Ready to Issue  1/28/2004 DONE
Telephone call  1/28/2004 DONE
Left message for Jack that permit is ready & fees//1/28/04 11:54am BAM
Plan resubmittals received  1/15/2004 DONE
INSP-Final Inspection1/9/20041/9/20041/9/2004APART
DetailsTroy Cobbley
A temporary occupancy was given until the fire alarm plans have been resubmitted showing the access control connected to the fire alarm. All other fire alarm devices have been tested
INSP-Alarm Testing1/7/20041/8/20041/8/2004AFAIL
DetailsTroy Cobbley
test phone lines, test batteries , submit plans showing the access control, provide alarm signal verification 1/8/2004 11:28:30 AM
Issue and Print Permit  11/12/2003 DONE
Inspection Record Card- Fire11/6/2003 11/6/2003 DONE
Permit Ready to Issue  11/6/2003 DONE
Telephone call  11/6/2003 DONE
left mess that permit is ready
Alarm Plan Check  11/5/2003 PASS
Approved pending field inspection of fire alarm permit comments.
Miscellaneous action  11/5/2003  
E-mail from Rick Jackson to Troy Cobbley on 10/8/2003 that he stopped at the site and found four wires from teh sproinkler riser to the east side lobby area. No devices were installed, but the wiring was for fire alarm.
PLANS/APPL TAKEN TO FRONT DESK  11/5/2003 DONE
Plan assigned to (SAM)9/25/2003 11/5/2003 DONE
Plan resubmittals received  10/28/2003 DONE
Alarm Plan Check  10/8/2003 FAIL
Resubmittal required. Faxed comments to Jack Schmidt 10/8/2003.
Application received  9/25/2003