Information based on query as of Friday, September 25, 2026.
Permit Information
Permit NumberFIR03-00612
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1755 N LINDA VISTA LN
Project Namealm - Dogwood Plaza Apartments
Customer Number 
ePlanReview 
Description
Provide a fire alarm system which will include sprinkler monitoring, elevator recall and shutdown, HVAC shutdown, fire/smoke damper release, audible alarms throughout the building with visuals required in all common and public areas. The dwelling units shall have capability to support visible alarm notification appliances

3/2/2004 - Additional Scope: Required smoke detector in second elevator lobby for the first floor and an additional thirteen (13) in-duct smoke detectors for fire/smoke damper release.

3/10/2004 - Additional Scope: Five (5) required in-duct smoke detectors for fire/smoke damper release.

5/26/2004 - Change in Scope: Four (4) in-duct smoke detectors have been replaced by area detection smoke detectors with relay bases for fire/smoke damper release. Two (2) control relays for elevator shaft smoke detector "firemans hat" output are deleted.

The associated building permit (BLD 03-00602) is to construct a new 40,666 sq.ft. 3 story, wood framed, 50 unit apartment building for senior living. Each unit is 534 sq.ft. one bedroom, one bath. This building is fully fire sprinklered for area increase and must meet NFPA 13. All construction per the approved plans and attached comment list. MJP DRH02-00236 CUP02-00146 PC# 145-03 Dogwood Plaza *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing6/16/20046/17/20046/17/2004PPASS
DetailsTroy Cobbley
Fire alarm system finaled 6/17/2004 3:13:03 PM
DOC - Permit Finaled6/17/20046/17/20046/17/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 6/17/2004 3:13:07 PM
INSP-Final Inspection6/15/20046/16/20046/16/2004AFAIL
DetailsTroy Cobbley
Provide verification of signals, provide map at the facp, repair the fire/smoke dampers as listed on the plans and swap a/v's in room 109. Structural inspector said they would verify operation of the single station smoke detectors. This inspection lasted 5 1/2 hours. I was unable to perform the life safety and fire sprinkler inspections. 6/16/2004 3:34:18 PM
Alarm Plan Check  5/26/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/26/2004 DONE
Permit Ready to Issue  5/26/2004 DONE
Inspection Record Card- Fire5/26/2004 5/26/2004 DONE
CHANGE STATUS TO (ISS)  5/26/2004 DONE
already issued previously
Plan resubmittals received  5/24/2004 DONE
Telephone call  4/7/2004 DONE
Tim Bellinger, GC, Simplex has been sending in the resubmittals each change. I stated that they could save them up and send in as-built plans prior to asking for the inspection. As long as the plans are in, a temp occupancy could occur.
INSP-Conference4/2/20044/2/20044/2/2004PDONE
DetailsTroy Cobbley
I spoke with the fire alarm contractor about horn/strobe placement in laundry room 4/5/2004 10:57:15 AM
INSP-Conference3/29/20043/30/20043/30/2004ADONE
DetailsTroy Cobbley
The alarm contractor wanted to discuss a/v locations that have been blocked by a new soffit in two rooms. I told him that the a/v's could not be mounted on the soffit but had to be mounted on a wall between 80" and 96" 3/30/2004 3:11:38 PM
Issue and Print Permit  3/11/2004 DONE
Alarm Plan Check  3/10/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/10/2004 DONE
Inspection Record Card- Fire3/10/2004 3/10/2004 DONE
Permit Ready to Issue  3/10/2004 DONE
Telephone call  3/10/2004 DONE
spoke with Chris -- permit is ready
Issue permit  3/9/2004 DONE
Plan resubmittals received  3/5/2004  
Telephone call  3/3/2004 DONE
left mess that permit is ready
Inspection Record Card- Fire3/3/2004 3/3/2004 DONE
Permit Ready to Issue  3/3/2004 DONE
Alarm Plan Check  3/2/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/2/2004 DONE
Plan resubmittals received  2/26/2004  
Issue and Print Permit  2/2/2004 DONE
Plan assigned to (SAM)10/9/2003 12/10/2003 DONE
Alarm Plan Check  12/10/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/10/2003 DONE
Inspection Record Card- Fire12/10/2003 12/10/2003 DONE
Permit Ready to Issue  12/10/2003 DONE
Telephone call  12/10/2003 DONE
Spoke with Chris and told him that permit is ready and that there are no fees due to this being a new structure//12/09/03 10/45 am BAM
Plan resubmittals received  11/26/2003 DONE
Alarm Plan Check  10/22/2003 FAIL
Resubmittal Required. Faxed comments to Chris Willis 10/22/2003.
Application received  10/9/2003