INSP-Sprinkler Rough-in/Hydro | 10/29/2003 | 10/30/2003 | 10/30/2003 | A | PASS |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 10/29/2003 at 2:09:10 PM. Contact: ###-####.
|
DOC - Permit Finaled | 10/30/2003 | 10/30/2003 | 10/30/2003 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/30/2003 9:45:59 AM
|
INSP-Sprinkler Rough-in | 10/28/2003 | 10/29/2003 | 10/29/2003 | A | FAIL |
Troy Cobbley
|
|
|
see approved plans for locations where hanagers exceed 9" from sprinkler drop, see plans for location where two drops are supplied from the same 1" outlet 10/29/2003 11:51:42 AM
|
Issue permit | | | 10/28/2003 | | |
|
|
|
|
Sprinkler Plan Check | 10/22/2003 | | 10/23/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/23/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 10/23/2003 | | DONE |
|
|
|
Emailed copy of review notes to designer - 11:00 am.
|
Inspection Record Card- Fire | 10/23/2003 | | 10/23/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/23/2003 | | DONE |
|
|
|
called Tom E. permit ready & fee given 10-23-03 11:16
|
Plan resubmittals received | | | 10/22/2003 | | |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 10/15/2003 | | 10/17/2003 | | FAIL |
Bill Alexander
|
|
|
A. The plans lack any history information of design, (even though the same Company installed the original system)? Provide enough original design information that would allow the AHJ to know whether this designer is meeting minimum code! (IFC 105.4.2)
B. Information provided on the type of pipe or fittings installed or installing in this area would indicate "steel" (reference Plan Sheet #1, General Notes, Item #23)! This area was originally installed with CPVC! Provide corrected documents addressing the correct system information. (IFC 105.4.2)
C. Information provided on the type of hangers installing in this area would indicate "steel". Steel and CPVC have different requirements for spacing and location to fitting, etc., which is not addressed in this submittal. (IFC 105.4.2)
NOTE: Building permit (BLD03-02344) has not been reviewed or approved through the Building Department or Fire Department. Contractor is will take a risk if fire protection permitting is reviewed and released prior to project permit approval.
|
Miscellaneous action | | | 10/17/2003 | | DONE |
|
|
|
Took failed plans to front call desk for calling and returning. Emailed failed review to designer Tom Easton.
|
Telephone call | | | 10/17/2003 | | DONE |
|
|
|
Left message for Tom Easton that plans failed and need picked up
|
Application received | | | 10/15/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 10/15/2003 | | | | |
|
|
|
|