Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR03-00622
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 4696 W OVERLAND RD Unit: 130
Project NameSPR DISCOVER MORTGAGE
Customer Number 
ePlanReview 
Description
(DISCOVER MORTGAGE)(HILLCREST BUSINESS CENTER-1ST FLR) To modify and add fire sprinklers in a remodel of a 2,761-ft/2, office on the south side of the 1st floor per plans. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-02344.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro10/29/200310/30/200310/30/2003APASS
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 10/29/2003 at 2:09:10 PM. Contact: ###-####.
DOC - Permit Finaled10/30/200310/30/200310/30/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 10/30/2003 9:45:59 AM
INSP-Sprinkler Rough-in10/28/200310/29/200310/29/2003AFAIL
DetailsTroy Cobbley
see approved plans for locations where hanagers exceed 9" from sprinkler drop, see plans for location where two drops are supplied from the same 1" outlet 10/29/2003 11:51:42 AM
Issue permit  10/28/2003  
Sprinkler Plan Check10/22/2003 10/23/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/23/2003 DONE
Miscellaneous action  10/23/2003 DONE
Emailed copy of review notes to designer - 11:00 am.
Inspection Record Card- Fire10/23/2003 10/23/2003 DONE
Telephone call  10/23/2003 DONE
called Tom E. permit ready & fee given 10-23-03 11:16
Plan resubmittals received  10/22/2003  
DetailsBill Alexander
Sprinkler Plan Check10/15/2003 10/17/2003 FAIL
DetailsBill Alexander
A. The plans lack any history information of design, (even though the same Company installed the original system)? Provide enough original design information that would allow the AHJ to know whether this designer is meeting minimum code! (IFC 105.4.2)

B. Information provided on the type of pipe or fittings installed or installing in this area would indicate "steel" (reference Plan Sheet #1, General Notes, Item #23)! This area was originally installed with CPVC! Provide corrected documents addressing the correct system information. (IFC 105.4.2)

C. Information provided on the type of hangers installing in this area would indicate "steel". Steel and CPVC have different requirements for spacing and location to fitting, etc., which is not addressed in this submittal. (IFC 105.4.2)

NOTE: Building permit (BLD03-02344) has not been reviewed or approved through the Building Department or Fire Department. Contractor is will take a risk if fire protection permitting is reviewed and released prior to project permit approval.
Miscellaneous action  10/17/2003 DONE
Took failed plans to front call desk for calling and returning. Emailed failed review to designer Tom Easton.
Telephone call  10/17/2003 DONE
Left message for Tom Easton that plans failed and need picked up
Application received  10/15/2003  
Plan assigned to (Bill)10/15/2003