INSP-Final Inspection | 12/8/2003 | 12/8/2003 | 12/8/2003 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/8/2003 at 7:45:57 AM.
|
DOC - Permit Finaled | 12/8/2003 | 12/8/2003 | 12/8/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/8/2003 4:17:43 PM
|
Plan assigned to (Bill) | 12/3/2003 | | 12/5/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/3/2003 | | 12/5/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/5/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 12/5/2003 | | DONE |
|
|
|
Emailed revised review notes to Ross Farris.
|
Issue and Print Permit | | | 12/5/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/5/2003 | | 12/5/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/3/2003 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2003 | 12/1/2003 | 12/1/2003 | P | FAIL |
Rick Jackson
|
|
|
need resubmittals and calc's - not installed per plans (2 inch main not installed per plans and using sidewalls from west wall to cover to soffit0; overspaced in mezzanine; need heads installed in kitchen area per plans and above ductwork;
|
Issue and Print Permit | | | 10/28/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 10/20/2003 | | 10/27/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/23/2003 | | 10/27/2003 | | PASS |
Bill Alexander
|
|
|
10/23/2003 - Waiting for RECORDS to find origignal shell system plans, to verify origignal design and this proposed remodel work.
10/24/2003 - Shell plans and remodel existing piping plans do not match. Called Grinnell and asked them to verify asbuilts. Tom Easton called back 3:10pm and we derived, he had the same plans the City has, which means asbuilts were not requested by Rick Jackson. Called De Best Fire (Ross Farris) and indicated calcs will be required. He argued that changes are being made now (hold off on review) and the plans will change with proper number of heads per pipe size (matching existing design).
|
Plan resubmittals received | | | 10/27/2003 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/27/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 10/27/2003 | | DONE |
|
|
|
Emailed review comments to Ross Ferris.
|
Inspection Record Card- Fire | 10/27/2003 | | 10/27/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/27/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/27/2003 | | DONE |
|
|
|
Spoke with Alisha told permit ready & fees
|
Application received | | | 10/20/2003 | | |
|
|
|
|