INSP-Final Inspection | 2/9/2004 | 2/10/2004 | 2/10/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/9/2004 at 9:06:53 AM. Contact: ###-####.
|
DOC - Permit Finaled | 2/10/2004 | 2/10/2004 | 2/10/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/10/2004 3:58:53 PM
|
Permit Ready to Issue | | | 1/28/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/28/2004 | | 1/28/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/28/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 1/28/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/27/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments. Permit can not be finalized pending receipt of the Fire Alarm Permit Application for the Capital Terrace network connection to the Washington Mutual Building's FA system.
|
Plan resubmittals received | | | 1/14/2004 | | |
|
|
|
|
INSP-Final Inspection | 12/19/2003 | 12/22/2003 | 12/22/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/19/2003 at 10:10:16 AM. Contact: ###-####. need smoke detector above FACP; NAC #2 was reversed so the EOL is on device #1 and not #6 12/22/2003 8:58:43 AM
|
Miscellaneous action | | | 12/17/2003 | | DONE |
|
|
|
Received a copy of the generator information (requested, comment #12 on FA permit review, to be given to the PDS Fire Inspector at inspection) from Dave Miller that defines the generator capability. It does not meet the requirements of NFPA 72, 1999, but will meet the requirements of NFPA 72, 2002. Per Dave Miller this is acceptable. I will attach the generator information to the city's permit copy.
|
Plan assigned to (SAM) | 10/23/2003 | | 11/6/2003 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/6/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/6/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Inspection Record Card- Fire | 11/6/2003 | | 11/6/2003 | | DONE |
|
|
|
|
Telephone call | | | 11/6/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Permit Ready to Issue | | | 11/6/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/6/2003 | | DONE |
|
|
|
|
Application received | | | 10/23/2003 | | |
|
|
|
|