Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR03-00642
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 175 N CAPITOL BLVD Unit: 2 FLR
Project NameWASHINGTON MUTUAL BLDG
Customer Number 
ePlanReview 
Description
To upgrade A/V appliances and area detection on the second floor of a high rise that has an existing manual fire alarm system with sprinkler monitoring, HVAC shutdown, elevator recall/shutdown, door release, partial area automatic detection and notification appliances.

The associated building permit (BLD 03-00100) is to create a 1,310 square foot training room within an existing 10,728 square foot tenant space located on the 2nd floor of an 11 story, 112,000 square foot building. Work is to include interior nonbearing walls, interior doors, and light switches all per approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW** (WASHINGTON MUTUAL - TRAINING ROOM - 2ND FLR) This building is fire sprinklered because it is a high-rise.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20042/10/20042/10/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/9/2004 at 9:06:53 AM. Contact: ###-####.
DOC - Permit Finaled2/10/20042/10/20042/10/2004PPASS
DetailsRick Jackson
Finaled by inspector at 2/10/2004 3:58:53 PM
Permit Ready to Issue  1/28/2004 DONE
Inspection Record Card- Fire1/28/2004 1/28/2004 DONE
Telephone call  1/28/2004 DONE
left mess that permit is ready
Issue and Print Permit  1/28/2004 DONE
Alarm Plan Check  1/27/2004 PASS
Approved pending field inspection of fire alarm permit comments. Permit can not be finalized pending receipt of the Fire Alarm Permit Application for the Capital Terrace network connection to the Washington Mutual Building's FA system.
Plan resubmittals received  1/14/2004  
INSP-Final Inspection12/19/200312/22/200312/22/2003AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/19/2003 at 10:10:16 AM. Contact: ###-####. need smoke detector above FACP; NAC #2 was reversed so the EOL is on device #1 and not #6 12/22/2003 8:58:43 AM
Miscellaneous action  12/17/2003 DONE
Received a copy of the generator information (requested, comment #12 on FA permit review, to be given to the PDS Fire Inspector at inspection) from Dave Miller that defines the generator capability. It does not meet the requirements of NFPA 72, 1999, but will meet the requirements of NFPA 72, 2002. Per Dave Miller this is acceptable. I will attach the generator information to the city's permit copy.
Plan assigned to (SAM)10/23/2003 11/6/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  11/6/2003 DONE
Alarm Plan Check  11/6/2003 PASS
Approved pending field inspection of fire alarm permit comments.
Inspection Record Card- Fire11/6/2003 11/6/2003 DONE
Telephone call  11/6/2003 DONE
left mess that permit is ready
Permit Ready to Issue  11/6/2003 DONE
Issue and Print Permit  11/6/2003 DONE
Application received  10/23/2003