Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR03-00646
StatusFinaled
Name ALARM SYSTEMS INTEGRATION INC
Site Address 705 W BANNOCK ST
Project Namealm - Satchels
Customer Number 
ePlanReview 
Description
The scope per conditional approval by Dave Miller (BFD) is to allow a temporary connection for monitoring of a hood suppression system to an existing non-compliant building fire alarm system contingent upon a building Fire Alarm System upgrade agreement being signed between the building owner and Boise Fire Department within 90 days.

The associated building permit (BLD 03-00430) is to convert an existing 1,490 square foot tenant space to a restaurant. This space is located on the first floor of a 3 story building (one story portion). The dining area is 839 square feet with an occupant load of 56. The total tenant space occupant load, including the kitchen, is 58. The occupant load of the dining room (56) shall be posted in a conspicuous place, on an approved sign, near the main exit from the room. Work is to include 2 restrooms accessible to the disabled, a grease hood and duct, millwork, suspended ceilings, interior walls, exterior wall infill, and interior finishes all per approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW** (SATCHEL'S GRILL) This building is fire sprinklered to substitute for 1-hr fire-resistive construction.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  10/11/2006  
Case Summary  1/31/2006 DONE
INSP-Alarm Testing5/5/20045/6/20045/6/2004APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/5/2004 at 1:08:14 PM. Contact: ###-####. Satchel's hood system connected to zone 5 as shown on plans; awaiting upgrade agreement for the exsisting building alarm system 5/6/2004 11:01:42 AM
DOC - Permit Finaled5/6/20045/6/20045/6/2004APASS
DetailsRick Jackson
Finaled by inspector at 5/6/2004 11:01:49 AM
Telephone call  5/4/2004 DONE
left mess that permit is ready
Issue and Print Permit  5/4/2004 DONE
Inspection Record Card- Fire5/3/2004 5/3/2004 DONE
Permit Ready to Issue  5/3/2004 DONE
Inspection Record Card- Fire5/3/2004 5/3/2004 DONE
Plan assigned to (SAM)10/28/2003 5/3/2004 DONE
Alarm Plan Check  5/3/2004 PASS
Conditional approval pending field inspection of fire alarm permit comments and a building Fire Alarm System upgrade agreement being signed between the building owner and the Boise Fire Department within 90 days.
PLANS/APPL TAKEN TO FRONT DESK  5/3/2004 DONE
Meeting  4/30/2004 DONE
Meeting with PDS staff. Decided to have the FI issue a final notice of violation (NOV) indicating power will be disconnected within 72 hours of receipt of the NOV, unless a temporary connection, approved by the fire department, is made to connect the cooking hood extinguishing system to the existing non-code compliant building fire alarm system within the 72 hour period. IF the connection is made, tested and approved within the allotted 72 hours, a TOC will be issued contingent upon a building fire alarm system upgrade agreement being signed between the building owner and the FD. The FD will address the requirement to upgrade the building fire alarm system separately and directly with the building owner. Dave Miller approved the connection shown on FA plans on temporary basis; okay to issue permit to allow connection to be installed.
Telephone call  11/13/2003 DONE
Telcon with Dave Miller re-plan submittal which shows improper interconnection of two FAC panels and does not show required sprinkler monitoring. Dave will allow us to approve this permit for the proposed connection of the new hood extinguishing system only after he approves an upgrade agreement for the building alarm system. I tried calling Ken Howell 3 times, not available, finally left voice mail with this message and to call Dave Miller to discuss the upgrade agreement. Plans to be held pending receipt of upgrade agreement approved by FD.
Application received  10/28/2003