Permit Information
Permit NumberFIR03-00648
StatusFinaled
Name PROTEX
Site Address 10356 W FAIRVIEW AVE Unit: 100
Project Namealm - VILLAGE SHOPPING CENTER
Customer Number 
ePlanReview 
Description
To provide a new required sprinkler monitoring fire alarm system with HVAC shutdown in an existing building.

The associated building permit (BLD 03-01026) is to remodel an existing 5,883 square foot one story building. Three (3) separate "shell" tenant spaces are being created (Suite 100 - 2,951 square feet, Suite 104 - 1,246 square feet, Suite 105 - 1,606 square feet). The specific tenants have NOT been disclosed. Separate tenant improvement permits OR occupancy approval permits are required for each tenant space before occupancy. A CERTIFICATE OF OCCUPANCY SHALL NOT BE ISSUED TO ANY PORTION OF THIS BUILDING UNTIL THE EAST PROPERTY LINE HAS BEEN MOVED AWAY FROM THE EAST EXTERIOR WALL OR THIS ISSUE OTHERWISE RESOLVED. Work is to include new beams, columns, and concrete footings at new exterior openings; new store front glazing systems at new exterior openings; new Exterior Insulation and Finish System; new interior beam and columns to replace a bearing wall; 6 (or perhaps 5) restrooms accessible to the disabled; interior nonbearing walls; and suspended ceilings all per approved drawings, engineering, and plan review conditions on file. A demolition permit (BLD03-01079) was issued earlier. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. DRH03-00048 **CJW** (DBSI - NO TENANT - SUITE100) This building is fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/5/20044/6/20044/6/2004APASS
DetailsTroy Cobbley
Fire alarm finaled 4/6/2004 12:05:50 PM
DOC - Permit Finaled4/6/20044/6/20044/6/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 4/6/2004 12:05:55 PM
INSP-Final Inspection4/2/20044/2/20044/2/2004PFAIL
DetailsTroy Cobbley
Started dtest but found multiple problems such as horn not working, smoke detector too far from deck, no breaker lock, no zone descriptions and per the general contractor the electrician still needed to program some items into the panel. The test needs to be started over 4/2/2004 3:07:09 PM
Issue and Print Permit  3/24/2004 DONE
Plan resubmittals received  3/23/2004 DONE
Alarm Plan Check  3/23/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/23/2004 DONE
Permit Ready to Issue  3/23/2004 DONE
Telephone call  3/23/2004 DONE
left a message for Rob -- permit is ready.
INSP-Final Inspection12/19/200312/19/200312/19/2003PPART
DetailsTroy Cobbley
Temp occupancy given until the fire alarm and fire sprinklers are finaled
Issue and Print Permit  12/12/2003 DONE
Plan assigned to (SAM)10/28/2003 12/11/2003 DONE
Alarm Plan Check  12/11/2003 PASS
Approved pending field inspection of fire alarm permit comments.
Telephone call  12/11/2003 DONE
Spoke with Rob Ahten, requested a cut sheet for the smoke detector above the panel and stated that the plans showed a horn, the riser and cutsheets imply a horn/strobe. The preferred appliance is a horn, he will need to provide cut sheets to the PDS Fire Inspector for field verification. Calcs will be acceptable as the horn takes less current than a horn/strobe.
PLANS/APPL TAKEN TO FRONT DESK  12/11/2003 DONE
Inspection Record Card- Fire12/11/2003 12/11/2003 DONE
Permit Ready to Issue  12/11/2003 DONE
Telephone call  12/11/2003 DONE
left message for Rob -- permit is ready.
Plan resubmittals received  12/2/2003 DONE
Alarm Plan Check  11/13/2003 FAIL
Resubmittal required. Faxed comments to Rob Ahten 11/13/2003.
Application received  10/28/2003