INSP-Final Inspection | 4/5/2004 | 4/6/2004 | 4/6/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled 4/6/2004 12:05:50 PM
|
DOC - Permit Finaled | 4/6/2004 | 4/6/2004 | 4/6/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 4/6/2004 12:05:55 PM
|
INSP-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 | P | FAIL |
Troy Cobbley
|
|
|
Started dtest but found multiple problems such as horn not working, smoke detector too far from deck, no breaker lock, no zone descriptions and per the general contractor the electrician still needed to program some items into the panel. The test needs to be started over 4/2/2004 3:07:09 PM
|
Issue and Print Permit | | | 3/24/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/23/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/23/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/23/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/23/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/23/2004 | | DONE |
|
|
|
left a message for Rob -- permit is ready.
|
INSP-Final Inspection | 12/19/2003 | 12/19/2003 | 12/19/2003 | P | PART |
Troy Cobbley
|
|
|
Temp occupancy given until the fire alarm and fire sprinklers are finaled
|
Issue and Print Permit | | | 12/12/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 10/28/2003 | | 12/11/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/11/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Telephone call | | | 12/11/2003 | | DONE |
|
|
|
Spoke with Rob Ahten, requested a cut sheet for the smoke detector above the panel and stated that the plans showed a horn, the riser and cutsheets imply a horn/strobe. The preferred appliance is a horn, he will need to provide cut sheets to the PDS Fire Inspector for field verification. Calcs will be acceptable as the horn takes less current than a horn/strobe.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/11/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/11/2003 | | 12/11/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/11/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/11/2003 | | DONE |
|
|
|
left message for Rob -- permit is ready.
|
Plan resubmittals received | | | 12/2/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/13/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten 11/13/2003.
|
Application received | | | 10/28/2003 | | |
|
|
|
|