Permit Information
Permit NumberFIR03-00675
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1503 W MAIN ST
Project Namealm - Rug Decor
Customer Number 
ePlanReview 
Description
To provide a new required sprinkler monitoring fire alarm system with HVAC shutdown smoke detectors.

The associated building permit (BLD 03-02277) is to include a new stairway to serve the basement, 2 restrooms accessible to the disabled, a new entry vestibule, new store front glazing, and interior nonbearing walls all per the approved drawings and the plan review report on file. For egress reasons, only 1,124 square feet of the basement will be occupied at this time. **CJW** (SAFIRE LLC) This building is NOT fire sprinklered. The entire basement shall be fire sprinklered in conjunction with this permit. To create a 4,182 square foot retail sales tenant space located within a 9,530 square foot one story building (4,765 square foot main floor and 4,765 square foot basement). This tenant space will have 3,058 square feet on the main floor and 1,124 square feet in the basement.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing12/15/200312/16/200312/16/2003PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/15/2003 at 3:34:41 PM. Contact: ###-####.
DOC - Permit Finaled12/16/200312/16/200312/16/2003PPASS
DetailsRick Jackson
Finaled by inspector at 12/16/2003 3:14:10 PM
Issue and Print Permit  12/8/2003 DONE
Plan assigned to (Mary)11/6/2003 12/2/2003 DONE
Alarm Plan Check  12/2/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/2/2003 DONE
Inspection Record Card- Fire12/2/2003 12/2/2003 DONE
Permit Ready to Issue  12/2/2003 DONE
Telephone call  12/2/2003 DONE
Spoke with John Lopez and told him that permit is ready & fees
Telephone call  11/20/2003 DONE
Telecon with John Lopez. Received the battery calculations, one slight problem, initially a 12 a-h battery is designed for. He will supply an 18 a-h battery. He will fax over cut sheets for the battery and information from the FACP for maximum battery charging capacity.
Miscellaneous action  11/20/2003 DONE
Received cut sheets for upgraded battery size.
INSP-Conference11/19/200311/19/200311/19/2003ADONE
DetailsRick Jackson
Stopped the job site for another inspection at 1501 Main (Beiter Office TI) and noticed the tamper conduit was run to the wall mount PIV. I went to the basement and saw wire run for the new smoke detector and a pull box installed at the riser with wires. There were two modules installed that appear for duct detectors with wires. Notified Mary of the work without permit.
Miscellaneous action  11/19/2003 DONE
Received battery calculations and external battery cabinet information.
Telephone call  11/18/2003 DONE
Request for cut sheet that defines maximum battery size or cut sheet for external battery cabinet. Need revised battery calculation, missing DLD Dialer info. Spoke with John Lopez.
Application received  11/6/2003