INSP-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 | A | PASS |
Rick Jackson
|
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
DOC - Permit Finaled | 12/17/2004 | 12/17/2004 | 12/17/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/17/2004 8:10:13 AM
|
INSP-Final Inspection | 5/18/2004 | 5/18/2004 | 5/18/2004 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 5/18/2004 at 10:32:20 AM. Contact: ###-####. Need strobe lowered to 96 inches in conference room; update maps 5/19/2004 7:28:53 AM
|
INSP-Conference | 5/6/2004 | 5/6/2004 | 5/6/2004 | P | PART |
Rick Jackson
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Met with Dan and reviewed plans; the exsisting horn/strobes in computer room aren't shown on any NAC panel. He will talk to Simplex about it. 5/6/2004 4:06:34 PM
|
Inspection Record Card- Fire | 2/27/2004 | | 2/27/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/27/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/27/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/27/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/27/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/19/2004 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 2/19/2004 | | 2/19/2004 | | DONE |
|
|
|
|
INSP-Conference | 2/11/2004 | 2/11/2004 | 2/11/2004 | P | PART |
Rick Jackson
|
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes reviewed plan review notes with Chris and have agreed on placement of strobes and will be included in resubmiitals 2/11/2004 3:12:48 PM
|
Issue permit | | | 12/31/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 11/13/2003 | | 12/30/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/30/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/30/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/30/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/30/2003 | | 12/30/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/30/2003 | | DONE |
|
|
|
Left message for Chris Willis that permit is ready & fees//12/30/03 1:20pm BAM
|
Plan resubmittals received | | | 12/16/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/28/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Chris Willis 11/28/2003.
|
Application received | | | 11/13/2003 | | |
|
|
|
|