INSP-Final Inspection | 6/23/2004 | 6/23/2004 | 6/23/2004 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 6/23/2004 | 6/23/2004 | 6/23/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/23/2004 3:09:35 PM
|
INSP-Final Inspection | 2/10/2004 | 2/11/2004 | 2/11/2004 | A | FAIL |
Rick Jackson
|
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need NFPA 72 Record of Completion; zones defined and knox box up 2/11/2004 4:13:26 PM
|
Issue and Print Permit | | | 1/7/2004 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 11/13/2003 | | 1/6/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/6/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/6/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Inspection Record Card- Fire | 1/6/2004 | | 1/6/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/6/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/6/2004 | | DONE |
|
|
|
spoke with Brian --- permit is ready.
|
Telephone call | | | 12/16/2003 | | DONE |
|
|
|
Phones AIC to inform them that they should always include a fire alarm permit application with any submittal and resubmittal. Also, a typical resubmittal will include two complete sets of drawings and related documentation.
|
Plan resubmittals received | | | 12/15/2003 | | DONE |
|
|
|
Partial resubmittal submitted, new riser and cut sheets for new panel.
|
Telephone call | | | 12/3/2003 | | DONE |
|
|
|
Kent Burton AIC, called to say the backflow preventer has not been included. Therefore, a new design will need to be implemented. They will resubmit.
|
Alarm Plan Check | | | 12/3/2003 | | FAIL |
|
|
|
Panel is maxed out and the backflow preventer has not been included. AIC will resubmit with new design.
|
Telephone call | | | 11/26/2003 | | DONE |
|
|
|
Telecon with Brian Richards AIC, a 4 zone panel is being installed, all zones are used and the IFC requires the backflow preventer valves to be monitored and annunciated separately. He will check into this.
|
Application received | | | 11/13/2003 | | |
|
|
|
|