INSP-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled 3/10/2004 2:20:31 PM
|
DOC - Permit Finaled | 3/10/2004 | 3/10/2004 | 3/10/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/10/2004 2:20:36 PM
|
INSP-Final Inspection | 3/3/2004 | 3/4/2004 | 3/4/2004 | A | FAIL |
Troy Cobbley
|
|
|
still need the backflow preventor friction loss verified since a different backflow preventor was installed. The flow switch did not activate the alarms (smoke detectors) 3/4/2004 8:46:20 AM
|
INSP-Final Inspection | 3/4/2004 | 3/4/2004 | 3/4/2004 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with dave miller's permission until the backflow can be verified and the alarms work.
|
INSP-Sprinkler Rough-in/Hydro | 2/23/2004 | 2/24/2004 | 2/24/2004 | P | FAIL |
Troy Cobbley
|
|
|
connect flow switch to the alarm system per review note #16. Flush underground per note #12. Lock valves of backflow preventor in open position. Remove ball valve that is in place before the backflow preventor. Provide data sheet for the backflow preventor since what is installed in not what was submitted. Provide correct orfice on the inspectors test. 2/24/2004 3:50:36 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/11/2003 | 12/16/2003 | 12/16/2003 | P | PASS |
Troy Cobbley
|
|
|
sprinkler piping is ok to cover 12/16/2003 12:37:12 PM
|
Inspection Record Card- Fire | 11/21/2003 | | 11/21/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/21/2003 | | DONE |
|
|
|
|
Telephone call | | | 11/21/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 11/21/2003 | | DONE |
|
|
|
|
Application received | | | 11/20/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 11/20/2003 | | 11/20/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/20/2003 | | 11/20/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/20/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 11/20/2003 | | DONE |
|
|
|
EMAILED COPY OF REVIEW NOTES TO ROSS FARRIS.
|