INSP-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 | A | PASS |
Rick Jackson
|
|
|
Please contact Ralph with scheduled time for reinspection. Thank you; Phone #: ###-#### Internet Inspection Request from: Teresa Costello All items corrected 3/10/2004 10:44:07 AM
|
DOC - Permit Finaled | 3/10/2004 | 3/10/2004 | 3/10/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/10/2004 10:44:13 AM
|
INSP-Final Inspection | 3/8/2004 | 3/9/2004 | 3/9/2004 | A | FAIL |
Rick Jackson
|
|
|
Contact Ralph with scheduled time.; Phone #: ###-#### Internet Inspection Request from: Teresa Costello Need 40 amp hr batteries; detectors within 3 ft of diffusers; record of completion; knox box 3/9/2004 10:20:50 AM
|
Plan assigned to (SAM) | 11/21/2003 | | 1/21/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/21/2004 | | DONE |
|
|
|
Called and spoke with Bill. An access controlled egress door has been added to the building on the resubmittal. The matrix does not show the output to unlock the door. Bill stated he would fax the matrix over.
|
Alarm Plan Check | | | 1/21/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/21/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/21/2004 | | 1/21/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/21/2004 | | DONE |
|
|
|
CALLED ALAN PERMIT READY & FEES GIVEN 1-21-04 11:12 ///DLD
|
Issue and Print Permit | | | 1/21/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/7/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/4/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Alan Mannor 12/4/2003.
|
Application received | | | 11/21/2003 | | |
|
|
|
|