INSP-Final Inspection | 2/10/2004 | 2/11/2004 | 2/11/2004 | A | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 2/11/2004 11:13:58 AM
|
DOC - Permit Finaled | 2/11/2004 | 2/11/2004 | 2/11/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 2/11/2004 11:14:09 AM
|
INSP-Final Inspection | 2/5/2004 | 2/6/2004 | 2/6/2004 | A | FAIL |
Troy Cobbley
|
|
|
move smoke detector to deck, provide temporal tone for horn, provide map for system per note #3, provide verification of standby currnet draw for battery sizing 2/6/2004 1:45:41 PM
|
Issue and Print Permit | | | 1/20/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/31/2003 | | 12/31/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/31/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/31/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Plan assigned to (SAM) | 11/21/2003 | | 12/30/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/30/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/30/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 12/30/2003 | | DONE |
|
|
|
Received e-mail with approval from Dave MIller to allow a 24 hour stand-by on the battery calculations.
|
Telephone call | | | 12/9/2003 | | DONE |
|
|
|
Spoke with Keith Olstrom, battery calculations are based on 24 hours, he may request permission from Dave Miller to allow the 24 hours stand-by as the NFPA goes to 24 hours 1/1/04. The other option is to redo the calculation for 60 hours, upgrade the battery size which means adding an external battery cabinet. Keith will advise me when he has an answer.
|
Application received | | | 11/21/2003 | | |
|
|
|
|