INSP-Final Inspection | 3/19/2004 | 3/22/2004 | 3/22/2004 | A | PASS |
Rick Jackson
|
|
|
rand; Phone #: ###-#### Internet Inspection Request from: Barbara Moore completed on 3/19 3/22/2004 11:33:41 AM
|
INSP-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/19/2004 3:51:43 PM
|
INSP-Final Inspection | 3/17/2004 | 3/17/2004 | 3/17/2004 | P | FAIL |
Rick Jackson
|
|
|
RAND; Phone #: ###-#### Internet Inspection Request from: Darla Downs Need keys in knox box; lock on can; remove old pulls; protect wiring 3/17/2004 4:49:35 PM
|
INSP-Final Inspection | 3/11/2004 | 3/15/2004 | 3/15/2004 | P | FAIL |
Rick Jackson
|
|
|
Mike, ###-#### voltage drop nearly 3 volts; NAC's not wired per plans 3/15/2004 4:39:11 PM
|
(F) Reprint permit | | | 3/11/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/11/2004 | | 3/11/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/30/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/30/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/30/2003 | | 12/30/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/30/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/30/2003 | | DONE |
|
|
|
Spoke with Rand and told him permit is ready & fees//12/30/03 9:39am BAM
|
Issue and Print Permit | | | 12/30/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 12/1/2003 | | 12/30/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/16/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/11/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/11/2003 | | FAIL |
|
|
|
Resubmittal required on comment #5. Faxed comments 12/11/03 to Rand Gruber at Alarm Star. I gave authorization to Alarm Star to begin installation, but no inspections until the permit is issued.
|
Telephone call | | | 12/10/2003 | | DONE |
|
|
|
I called Rand Gruber (Alarm Star - FA permit applicant) to request the following:
single station detector locations
cut sheets for batteries, panel capacities of battery charger and max battery size, single station detectors
FACP is shown in a NEMA 12 rated box on the outside of the building, no smoke detector, no environmental controls.
I stated I would leave one copy of the original submittal at the front desk for him to pick up.
|
Alarm Plan Check | | | 12/10/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed a copy of the comments to Rand Gruber 12/10/03
|
Telephone call | | | 12/2/2003 | | DONE |
|
|
|
Left message for Mike Cullen to call me about the fire alarm submittal. (Troy)
|
Application received | | | 12/1/2003 | | |
|
|
|
|