INSP-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 | A | PASS |
Troy Cobbley
|
|
|
fire alarm finaled
|
INSP-Final Inspection | 8/11/2005 | 8/11/2005 | 8/11/2005 | P | FAIL |
Troy Cobbley
|
|
|
dave; Phone #: ###-#### Provide map at the facp and repair/test both phone lines since they did not provide trouble when disconnected.
|
INSP-Final Inspection | 8/5/2005 | 8/8/2005 | 8/8/2005 | P | FAIL |
Forrest France
|
|
|
Provide stamped approved plans on site for inspection, HVAC units need to be operable for duct smoke detection testing, PIV tamper is not programed correctly, provide lock and label at breaker in panel for FACP, clear trouble at knox box, test remaining alarm devices.
|
Inspection Record Card- Fire | 7/7/2005 | | 7/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/7/2005 | | DONE |
|
|
|
Spoke with Sam and told him that permit is ready & fees///7/7/05 9:09am BAS
|
Alarm Plan Check | | | 7/7/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
(F) Reprint permit | | | 7/7/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/6/2005 | | DONE |
|
|
|
|
Case Summary | | | 7/6/2005 | | |
|
|
|
|
FIR-Aging Inspection | 8/17/2004 | 8/17/2004 | 8/17/2004 | | NR |
Troy Cobbley
|
|
|
Per the secretary at AIC's office they haven't started the install yet because the building is not built yet. 8/17/2004 4:00:00 PM
|
Inspection Record Card- Fire | 5/13/2004 | | 5/13/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/13/2004 | | DONE |
|
|
|
|
Telephone call | | | 5/13/2004 | | DONE |
|
|
|
permits fir03-00737 thru fir03-00744 ready or pick up and fee due
|
Issue and Print Permit | | | 5/13/2004 | | DONE |
|
|
|
|
Meeting | | | 5/12/2004 | | DONE |
|
|
|
Brian Richards (AIC) marked up both sets of drawings (plans and riser) to show the elevator controls. He also left copies cut sheets of the 851 smoke detector and the FCM control module.
|
Plan resubmittals received | | | 5/12/2004 | | DONE |
|
|
|
Brian Richards (AIC) marked up both sets of plans and risers and left copies of the control module and 851 smoke detector cut sheets.
|
Alarm Plan Check | | | 5/12/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/12/2004 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 12/1/2003 | | 5/12/2004 | | DONE |
|
|
|
|
Telephone call | | | 5/11/2004 | | DONE |
|
|
|
Called Brian Richards (AIC) to set up a meeting to get the drawings and associated documentation for Bown Crossing cleaned up, marked up and issued.
|
Alarm Plan Check | | | 5/11/2004 | | FAIL |
|
|
|
Elevator has been added in BLDG H. AIC has shown the control modules, but has not "labeled" them. Cut sheets for the 851 and control module are required. Called Brian and set up a meeting to get the drawings issued.
|
Plan resubmittals received | | | 5/3/2004 | | |
|
|
|
|
Alarm Plan Check | | | 2/26/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Brian Richard 2/26/2004.
|
Miscellaneous action | | | 2/20/2004 | | DONE |
|
|
|
Phone call with Brian Richard. The title block of the Bown Crossing drawings has Martin Wolfords NICET certificate number. Martin has not worked at AIC since 9/2003. Brian will resubmit new drawings with new title blocks.
|
Plan resubmittals received | | | 2/18/2004 | | |
|
|
|
|
Alarm Plan Check | | | 12/16/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Brian Richard, AIC 12/16/2003.
|
Miscellaneous action | | | 12/10/2003 | | DONE |
|
|
|
Faxed request for additional permit application information.
|
Application received | | | 12/1/2003 | | |
|
|
|
|