INSP-Final Inspection | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | PASS |
Troy Cobbley
|
|
|
office; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
DOC - Permit Finaled | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 2/12/2004 1:15:54 PM
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 2/12/2004 | | |
|
|
|
paid re-inpsection fee
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 2/12/2004 | | |
|
|
|
paid re-inspection fee
|
INSP-Final Inspection | 2/4/2004 | 2/5/2004 | 2/5/2004 | A | FAIL |
Troy Cobbley
|
|
|
Upright heads are still overspaced on the Bangkok Thialand side of the wall 2/5/2004 11:19:50 AM
|
INSP-Final Inspection | 2/3/2004 | 2/3/2004 | 2/3/2004 | P | FAIL |
Troy Cobbley
|
|
|
Upright sprinkler heads are overspaced on the Bangkok Thialand side of the common wall. Pendant heads are 8' off of the restroom walls in the dining area. Pendant head in the scullery (service area) exceeds the 130 max spacing. The area is to be considered ordinary group 1. I could not verify if the hangers were attached as requested to the top chord 2/3/2004 2:44:41 PM
|
INSP-Final Inspection | 1/28/2004 | 1/28/2004 | 1/28/2004 | P | FAIL |
Rick Jackson
|
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Annette Moore not allo fthe hangers were moved to top of truss; missing head at prep area - overspaced 1/28/2004 2:57:58 PM
|
Miscellaneous action | | | 1/26/2004 | | DONE |
|
|
|
Recieved an email requesting a change for minimum spacing of Light Hazard areas and allowed up to 225-ft/2 spacing per original design information provided from Jeff Anderson, T.V. Fire Protection.
|
INSP-Final Inspection | 1/22/2004 | 1/22/2004 | 1/22/2004 | P | FAIL |
Troy Cobbley
|
|
|
It appears that the upright sprinkler heads on the asian market side of new rated wall. The new pendant heads exceed the 129 sq. ft. max spacing as noted on the drawings. Hangers need to be attached to the top chord of the trusses or engineer approved 1/22/2004 2:25:31 PM
|
Sprinkler Plan Check | 12/12/2003 | | 12/15/2003 | | PASS |
Bill Alexander
|
|
|
Faxed
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/15/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 12/15/2003 | | DONE |
|
|
|
Emailed (PDF copy) review to Jeff Anderson
|
Inspection Record Card- Fire | 12/15/2003 | | 12/15/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/15/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/15/2003 | | DONE |
|
|
|
Left message for Jeff that permit is ready & fees
|
Issue permit | | | 12/15/2003 | | DONE |
|
|
|
|
Application received | | | 12/12/2003 | | |
|
|
|
Faxed documents
|
Plan assigned to (Bill) | 12/12/2003 | | | | |
|
|
|
|