INSP-Final Inspection | 7/26/2004 | 7/26/2004 | 7/26/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled
|
DOC - Permit Finaled | 7/26/2004 | 7/26/2004 | 7/26/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 7/26/2004 2:52:47 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/22/2004 | 7/22/2004 | 7/22/2004 | P | PART |
Troy Cobbley
|
|
|
Forward flush of the backflow preventer and the additional head in the closet are ok. Still need alarm connections and hanger from previous correction notice to be done. 7/22/2004 1:58:54 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2004 | 7/21/2004 | 7/21/2004 | A | PASS |
Troy Cobbley
|
|
|
Hydro test for the wet system passed. Provide forward flush of the backflow preventor per review note #9. Provide signage. Provide alarm interconnections between FACP and new dry pipe riser. Provide head in closet and provide hanger per previous correction notice. 7/21/2004 2:25:31 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2004 | 7/16/2004 | 7/16/2004 | P | PASS |
Troy Cobbley
|
|
|
24 hour test of the existing dry system is ok 7/16/2004 4:06:06 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/14/2004 | 7/15/2004 | 7/15/2004 | A | PART |
Troy Cobbley
|
|
|
Hydro tests for both dry systems are ok. 24 hour test on the second dry system started at 12:45 at 67psi 7/15/2004 12:44:05 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2004 | 7/13/2004 | 7/13/2004 | A | PART |
Troy Cobbley
|
|
|
24 hour air test on the new dry system is ok. Rough-in inspection on the remaining first floor offices is ok except for one additional head and one hanger that need to be added. See plans for location. 7/13/2004 9:45:57 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2004 | 7/13/2004 | 7/13/2004 | A | PART |
Troy Cobbley
|
|
|
24 hour air test on the new dry system is ok. Rough-in inspection on the remaining first floor offices is ok except for one additional head and one hanger that need to be added. See plans for location. 7/13/2004 9:45:57 AM
|
INSP-Sprinkler Rough-in | 7/9/2004 | 7/12/2004 | 7/12/2004 | A | PART |
Troy Cobbley
|
|
|
24 hour air test started at 9:00am with 47 1/2 psi 7/12/2004 9:41:27 AM
|
INSP-Sprinkler Rough-in | 6/18/2004 | 6/21/2004 | 6/21/2004 | A | PART |
Troy Cobbley
|
|
|
Sprinkler rough-in for first and second floor east side offices OK. See approved plans for specific locations. 6/21/2004 10:09:27 AM
|
INSP-Sprinkler Rough-in | 6/1/2004 | 6/2/2004 | 6/2/2004 | A | PART |
Rick Jackson
|
|
|
Contact: Chris; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley See approved plans for areas inspected - highlighted areas only 6/2/2004 11:29:20 AM
|
Meeting | | | 4/20/2004 | | DONE |
|
|
|
Per conversation with Debest AS fitter today, work is under way and is to be completed in approx. 5 weeks.
|
FIR-Aging Inspection | 3/30/2004 | 3/30/2004 | 3/30/2004 | | NR |
Troy Cobbley
|
|
|
Per Randy with Debest Fire work is in progress 3/30/2004 3:35:26 PM
|
Plan assigned to (Bill) | 2/19/2004 | | 3/1/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/19/2004 | | 3/1/2004 | | PASS |
Bill Alexander
|
|
|
*Approved unless riser modification for forward flow testing is required. Reference plan review notes number #9.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/1/2004 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/1/2004 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/1/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/1/2004 | | 3/1/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/1/2004 | | DONE |
|
|
|
permit ready for pickup no fees per bill a.
|
Plan resubmittals received | | | 2/19/2004 | | |
|
|
|
|
Issue and Print Permit | | | 12/30/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/26/2003 | | 12/26/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/26/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/26/2003 | | DONE |
|
|
|
Left message that permit is ready
|
Sprinkler Plan Check | 12/17/2003 | | 12/24/2003 | | PART |
Bill Alexander
|
|
|
Requires resubmittals. Reference attached (failed) review notes.
|
Application received | | | 12/17/2003 | | |
|
|
|
|