INSP-Final Inspection | 3/12/2004 | 3/15/2004 | 3/15/2004 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/12/2004 at 11:48:49 AM. Contact: ###-####.
|
DOC - Permit Finaled | 3/15/2004 | 3/15/2004 | 3/15/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/15/2004 8:19:09 AM
|
INSP-Final Inspection | 2/20/2004 | 2/23/2004 | 2/23/2004 | A | FAIL |
Rick Jackson
|
|
|
need horn in place of strobe per plan review notes; 17 amp hr batteries installed in place of 18 amp hr as shown on plans - exceeds requirements for 60 hr; zones changed per one-line: zone 1 is smoke and water flow changed and will be reflected on zone map when provided; knox box needed 2/23/2004 9:09:25 AM
|
INSP-Final Inspection | 2/19/2004 | 2/20/2004 | 2/20/2004 | A | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/19/2004 at 8:55:27 AM. Contact: ###-####. per Matt this is rescheduled for 2/23/04 2/20/2004 11:01:12 AM
|
Issue and Print Permit | | | 1/27/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 12/18/2003 | | 1/7/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/7/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Permit Ready to Issue | | | 1/7/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/7/2004 | | DONE |
|
|
|
left message for Dave at ADT -- permit is ready.
|
Inspection Record Card- Fire | 1/7/2004 | | 1/7/2004 | | DONE |
|
|
|
|
Application received | | | 12/18/2003 | | |
|
|
|
|