Permit Information
Permit NumberFIR03-00800
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 250 S 5TH ST Unit: (8TH FLR)
Project Namealm -C W MOORE PLAZA-8TH FLR
Customer Number 
ePlanReview 
Description
To add two door hold-opens with smoke detector for door release and visuals with voice evac to a required existing fire alarm system that includes requirements for high rise, elevator recall/shutdown, sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release and visuals with voice evac throughout.

The associated building permit (BLD 03-02373) is to construct a 2,886 square foot classroom tenant space located on the 8th floor of an existing 99,655 square foot, 9 story, high-rise building. Work is to include the extension of an existing 1-hr corridor, a new door into an existing 2-hr stair enclosure, interior walls, interior doors, suspended ceilings, and interior finishes all per the approved drawings and the plan review report on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW** (NORTHWEST NAZARENE UNIVERSITY - C W MOORE PLAZA - 8TH FLR) This building is fire sprinklered because it is a high-rise.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  4/20/2007  
INSP-Final Inspection1/14/20041/14/20041/14/2004PPASS
DetailsRick Jackson
DOC - Permit Finaled1/14/20041/14/20041/14/2004PPASS
DetailsRick Jackson
Finaled by inspector at 1/14/2004 4:33:10 PM
INSP-Final Inspection1/9/20041/12/20041/12/2004ANR
DetailsRick Jackson
Rick,
We need to request a 2:00 o'clock inspection at 8th floor C.W. Moore T.I.
Call me on my cell phone if you have any problems. ###-####

Thanks
Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
INSP-Final Inspection1/9/20041/9/20041/9/2004PFAIL
DetailsRick Jackson
speaker/strobes nit installed per listiing using extension ring with backbox causing short 1/9/2004 3:19:33 PM
Inspection Record Card- Fire1/8/2004 1/8/2004 DONE
Permit Ready to Issue  1/8/2004 DONE
Telephone call  1/8/2004 DONE
spoke with Jason -- permit is ready.
Issue and Print Permit  1/8/2004 DONE
Plan assigned to (Mary)12/23/2003 1/7/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/7/2004 DONE
Alarm Plan Check  1/7/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Application received  12/23/2003