Permit Information
Permit NumberFIR04-00010
StatusFinaled
Name PEAK ALARM
Site Address 1772 W STATE
Project Namealm - ALBERTSONS MARKETPLACE
Customer Number 
ePlanReview 
Description
To install a new required sprinkler monitoring fire alarm system in an existing building.
2/17/2004 - To replace and relocate an existing sprinkler monitoring fire alarm system. The new system will include sprinkler monitoring, HVAC shutdown and monitoring of a cooking hood. There are six (6) conventional smoke detectors located in the tenant spaces that will be removed. A Radionics FACP with smoke detector coverage will also be removed.

The associated building permit (BLD 03-02729) is to remodel a 1,365 sq. ft. existing sandwich shop for new restaurant tenant per approved plans. Work to include, installation of a new one-hour hood system and grease duct. Grease duct to be wrapped with fire master duct wrap. Miscellaneous related interior finishes. This building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (pc#707-03) rmh (MAZZEH RESTAURANT)(ALBERTSONS MARKETPLACE)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/25/20046/25/20046/25/2004PPASS
DetailsRick Jackson
DOC - Permit Finaled6/25/20046/25/20046/25/2004PPASS
DetailsRick Jackson
Finaled by inspector at 6/25/2004 4:04:06 PM
INSP-Alarm Testing6/23/20046/24/20046/24/2004PFAIL
DetailsRick Jackson
LINDA; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Duct detectors not shutting off HVAC units and the ARM's aren't showing activation with the LED 6/24/2004 4:04:36 PM
INSP-Final Inspection6/3/20046/8/20046/8/2004PFAIL
DetailsRick Jackson
Terry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Sprinkler bell not working; address wrong for dispatching from monitoring company; duct detectors relay not latching 6/8/2004 3:52:12 PM
Issue and Print Permit  5/21/2004 DONE
Alarm Plan Check  5/13/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/13/2004 DONE
Inspection Record Card- Fire5/13/2004 5/13/2004 DONE
Permit Ready to Issue  5/13/2004 DONE
Telephone call  5/13/2004 DONE
Permit ready and fee due
Plan resubmittals received  5/5/2004 DONE
Received refaxed FA permit application from PEAK alarm. It still stipulates a manual fire alarm system, audible/visual annunciation both of which are not the case.
Telephone call  4/30/2004 DONE
Called Keith Olstrom with Peak. The application does not define the occupancy, it calls for required manual fire alarm system and required automatic detection and audible/visual annunciation. I believe this to be a sprinkler monitoring system. I have asked Keith to clarify the smoke detectors in specific spaces (not all) and find out the occupancy then fill out the FA permit application to reflect the system required. I stated he could fax the application to me.
Miscellaneous action  4/29/2004 DONE
Faxed request for additional FA permit application information. Received revised app via fax.
Plan resubmittals received  4/22/2004  
INSP-Final Inspection4/14/20044/15/20044/15/2004AFAIL
DetailsRick Jackson
please call teri before going out ; Phone #: ###-#### Internet Inspection Request from: Darla Downs Resubmittals needed for 6 new tampers on the anti-freeze loop and deletion of the knox box tamper; sign on riser door; address was wrong the monitoring account 4/15/2004 1:52:39 PM
INSP-Final Inspection4/8/20044/9/20044/9/2004AFAIL
DetailsRick Jackson
Terry; Phone #: ###-#### please call first for access. Internet Inspection Request from: Aimee Hughes Extension given on temp occupancy for Mazzeh as the new alarm system isn't completed; tested the hood extinguishing system and it sent alarm signal to new panel; all of the water flows/tampers not connected to the new panel 4/9/2004 1:41:09 PM
PLANS/APPL TAKEN TO FRONT DESK  2/17/2004 DONE
Alarm Plan Check  2/17/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
Permit Ready to Issue  2/17/2004 DONE
Telephone call  2/17/2004 DONE
spoke with Peak Alarm -- permit is ready.
Issue and Print Permit  2/17/2004 DONE
Plan assigned to (Mary)2/11/2004 2/11/2004 DONE
Inspection Record Card- Fire1/20/2004 1/20/2004 DONE
Issue and Print Permit  1/20/2004 DONE
Plan assigned to (Mary)1/6/2004 1/20/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/20/2004 DONE
Alarm Plan Check  1/20/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Telephone call  1/20/2004 DONE
called keith permit ready 1-20-04 3:59 ///dld
Application received  1/6/2004  
Inspection Record Card- Fire1/20/2004