INSP-Final Inspection | 6/25/2004 | 6/25/2004 | 6/25/2004 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 6/25/2004 | 6/25/2004 | 6/25/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/25/2004 4:04:06 PM
|
INSP-Alarm Testing | 6/23/2004 | 6/24/2004 | 6/24/2004 | P | FAIL |
Rick Jackson
|
|
|
LINDA; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Duct detectors not shutting off HVAC units and the ARM's aren't showing activation with the LED 6/24/2004 4:04:36 PM
|
INSP-Final Inspection | 6/3/2004 | 6/8/2004 | 6/8/2004 | P | FAIL |
Rick Jackson
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Sprinkler bell not working; address wrong for dispatching from monitoring company; duct detectors relay not latching 6/8/2004 3:52:12 PM
|
Issue and Print Permit | | | 5/21/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/13/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/13/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/13/2004 | | 5/13/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/13/2004 | | DONE |
|
|
|
|
Telephone call | | | 5/13/2004 | | DONE |
|
|
|
Permit ready and fee due
|
Plan resubmittals received | | | 5/5/2004 | | DONE |
|
|
|
Received refaxed FA permit application from PEAK alarm. It still stipulates a manual fire alarm system, audible/visual annunciation both of which are not the case.
|
Telephone call | | | 4/30/2004 | | DONE |
|
|
|
Called Keith Olstrom with Peak. The application does not define the occupancy, it calls for required manual fire alarm system and required automatic detection and audible/visual annunciation. I believe this to be a sprinkler monitoring system. I have asked Keith to clarify the smoke detectors in specific spaces (not all) and find out the occupancy then fill out the FA permit application to reflect the system required. I stated he could fax the application to me.
|
Miscellaneous action | | | 4/29/2004 | | DONE |
|
|
|
Faxed request for additional FA permit application information. Received revised app via fax.
|
Plan resubmittals received | | | 4/22/2004 | | |
|
|
|
|
INSP-Final Inspection | 4/14/2004 | 4/15/2004 | 4/15/2004 | A | FAIL |
Rick Jackson
|
|
|
please call teri before going out ; Phone #: ###-#### Internet Inspection Request from: Darla Downs Resubmittals needed for 6 new tampers on the anti-freeze loop and deletion of the knox box tamper; sign on riser door; address was wrong the monitoring account 4/15/2004 1:52:39 PM
|
INSP-Final Inspection | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | FAIL |
Rick Jackson
|
|
|
Terry; Phone #: ###-#### please call first for access. Internet Inspection Request from: Aimee Hughes Extension given on temp occupancy for Mazzeh as the new alarm system isn't completed; tested the hood extinguishing system and it sent alarm signal to new panel; all of the water flows/tampers not connected to the new panel 4/9/2004 1:41:09 PM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/17/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
Permit Ready to Issue | | | 2/17/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2004 | | DONE |
|
|
|
spoke with Peak Alarm -- permit is ready.
|
Issue and Print Permit | | | 2/17/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 2/11/2004 | | 2/11/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/20/2004 | | 1/20/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/20/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 1/6/2004 | | 1/20/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/20/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/20/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Telephone call | | | 1/20/2004 | | DONE |
|
|
|
called keith permit ready 1-20-04 3:59 ///dld
|
Application received | | | 1/6/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 1/20/2004 | | | | |
|
|
|
|