INSP-Final Inspection | 7/13/2004 | 7/13/2004 | 7/13/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
DOC - Permit Finaled | 7/13/2004 | 7/13/2004 | 7/13/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 7/13/2004 9:46:31 AM
|
INSP-Final Inspection | 7/13/2004 | 7/13/2004 | 7/13/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
DOC - Permit Finaled | 7/13/2004 | 7/13/2004 | 7/13/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 7/13/2004 9:46:31 AM
|
INSP-Final Inspection | 7/13/2004 | 7/13/2004 | 7/13/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
DOC - Permit Finaled | 7/13/2004 | 7/13/2004 | 7/13/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 7/13/2004 9:46:31 AM
|
Issue and Print Permit | | | 7/8/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/6/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/6/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/6/2004 | | 7/6/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/6/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/6/2004 | | DONE |
|
|
|
PERMIT READY AND FEE DUE
|
Telephone call | | | 7/1/2004 | | DONE |
|
|
|
Phoned Rob Ahten to inquire the locaiton of a shutdown relay module not shown on the plans and to request a revised matrix that defines the fire/smoke door (roll-up at the kitchen). I will red-line his prints to get the module on the sheet, he will send me a matrix in 5 minutes.
|
Miscellaneous action | | | 7/1/2004 | | DONE |
|
|
|
Received revised matrix.
|
Plan resubmittals received | | | 6/30/2004 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/30/2004 | | DONE |
|
|
|
Phone call to Rob Ahten to request a revised matrix that includes the door release functionality.
|
INSP-Final Inspection | 6/29/2004 | 6/29/2004 | 6/29/2004 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with dave millers permission. Fire alarm plan modifications have been resubmitted to the city of boise. If school is to be occupied prior to final sign off a fire watch will be required.
|
Alarm Plan Check | | | 6/29/2004 | | FAIL |
|
|
|
Resubmittal required. Drawing for Area E does not show the walls, can not verify or confirm proper smoke detector spacing or notification coverage. Phone call to Rob Ahten, he stated he would have 2 "Area E" drawings resubmitted tomorrow.
|
INSP-Final Inspection | 6/28/2004 | 6/28/2004 | 6/28/2004 | P | FAIL |
Troy Cobbley
|
|
|
Need fire alarm resubmittals approved. All other items are OK.
|
INSP-Final Inspection | 6/24/2004 | 6/25/2004 | 6/25/2004 | A | FAIL |
Rick Jackson
|
|
|
Rick This is Grants cell. Have a Great Day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Need cages on strobes in auditorium; provide as-builts for NAC's to owner 6/25/2004 4:39:58 PM
|
Plan resubmittals received | | | 6/25/2004 | | |
|
|
|
|
INSP-Final Inspection | 6/23/2004 | 6/24/2004 | 6/24/2004 | P | FAIL |
Troy Cobbley
|
|
|
Resubmit plans showing additional devices. Backflow preventors to annunciate separately. Provide in-duct detectors instead of duct detectors at the fire/smoke dampers. Smoke detectors are over spaced in hall 165, library and outside of the admin. office. Provide signage on fire sprinkler riser door. No notification devices have been verified for spacing or function. 6/24/2004 3:08:35 PM
|
INSP-Final Inspection | 6/22/2004 | 6/23/2004 | 6/23/2004 | P | CANC |
Troy Cobbley
|
|
|
This is Robs cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
Issue and Print Permit | | | 5/14/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/12/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/12/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/12/2004 | | 5/12/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/12/2004 | | |
|
|
|
|
Telephone call | | | 5/12/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Plan resubmittals received | | | 5/3/2004 | | DONE |
|
|
|
Terry from Protex changed out the plans and resubmitted plans and riser that includes clouds and revs.
|
Telephone call | | | 4/28/2004 | | DONE |
|
|
|
Called Rob Ahten and requested that he define the clouds on his plans with the proper revs. At this time there is no rev block or date and many changes that are clouded that do not pertain to the plan modification. He stated he would stop by tomorrow.
|
Plan resubmittals received | | | 4/20/2004 | | |
|
|
|
|
Issue and Print Permit | | | 3/3/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/2/2004 | | 3/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/2/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Mary) | 1/6/2004 | | 3/1/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/1/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/1/2004 | | 3/1/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/1/2004 | | |
|
|
|
|
Plan resubmittals received | | | 2/23/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/21/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten 1/21/2004.
|
Application received | | | 1/6/2004 | | |
|
|
|
|