Permit Information
Permit NumberFIR04-00021
StatusFinaled
Name PROTEX
Site Address 707 N ARMSTRONG PL
Project NamealmIdaho Public Health Dist #4
Customer Number 
ePlanReview 
Description
FA Scope is undefined at this time. Plans show three (3) duct detectors in the new space.
2/9/2004 - To extend the existing required fire alarm system into the new space with notification throughout and HVAC shutdown for three (3) duct detectors. The existing system includes HVAC shutdown, sprinkler monitoring, partial area detection and notification. Four (4) pull stations and two (2) smoke detectors were added in the existing area. (Exterior exits and FACP, control panels for the fire alarm system).

4/30/2004 - Plan Modification: A new NAC panel is being added to accommodate the voltage drop issue from the FA inspection, sprinkler monitoring points for a new dry system, PIV and backflow preventer valves.

5/25/2004 - Plan Modification: Architectural change. A single office has been divided in to two. A new NAC appliance is added to accommodate visual and audible coverage.

The associated building permit (BLD 03-01797) is to construct a 3500 square foot, one story office addition on the north side of the existing 39,500 square foot, one story Central District Health office building and related site improvements. The sprinklers are used for allowable area increase. This building is now at the maximum allowable area under the 2000 IBC. All construction per the approved plans and attached comment list. DRH03-00123/CUP03-00064/PC#427-03/JCM Central District Health Department (Addition) *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/28/20046/29/20046/29/2004APASS
DetailsTroy Cobbley
Fire alarm finaled 6/29/2004 9:59:06 AM
DOC - Permit Finaled6/29/20046/29/20046/29/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 6/29/2004 9:59:10 AM
INSP-Final Inspection6/15/20046/18/20046/18/2004AFAIL
DetailsTroy Cobbley
Provide a/v coverage in the corridor per the last correction notice. Change the 30cd strobe to 15cd in Rob's office. Provide signage on doors to facp and sprinkler riser per review note #23. Test low air signal on dry pipe riser 6/18/2004 9:33:41 AM
INSP-Final Inspection6/9/20046/14/20046/14/2004ACANC
DetailsTroy Cobbley
Inspection was cancelled by Rob with Protex 6/14/2004 8:33:34 AM
Issue and Print Permit  5/28/2004 DONE
Alarm Plan Check  5/25/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/25/2004 DONE
Permit Ready to Issue  5/25/2004 DONE
Telephone call  5/25/2004 DONE
permit ready and fee due
Plan resubmittals received  5/20/2004  
Issue and Print Permit  5/5/2004 DONE
Alarm Plan Check  4/30/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/30/2004 DONE
Permit Ready to Issue  4/30/2004 DONE
Telephone call  4/30/2004 DONE
left a message for Rob -- permit is ready.
Plan resubmittals received  4/15/2004  
INSP-Final Inspection3/12/20043/18/20043/18/2004AFAIL
DetailsTroy Cobbley
Resubmit fire alarm plans that include all devices including the second dry pipe valve, backflow preventor and the additional three duct smoke detectors. End of line voltage on the notification circuits exceeds 21.6 volts(nfpa 72, 7.3.2.3). Provide verification/explanation on resubmittals on why remaining hvac units do not have automatic shutdown per IMC. Office and corridor areas that open into the new addition must be brought up to code compliance. Only the items listed above have been inspected and addressed. All other items to be verified when resubmitted plans have been issued 3/18/2004 9:41:04 AM
Miscellaneous action  2/13/2004 DONE
Requirement of comment #18 (duct detectors shall be provided as requried by the Code under which the units were installed.

Areas -front entry customer waiting and Nursing admin area are fed by multiple units that summed are over 2000 cfm. Per the 1991 UMC, single systems over 2000 cfm are to be monitored for shutdown.

Therefore the monitoring air handlers for these two areas will not be required.
INSP-Final Inspection2/12/20042/12/20042/12/2004APART
DetailsTroy Cobbley
Temporary occupancy was given until all of the fire mains are upgraded per plans submitted to boise city and the fire alarm system is completed
Plan assigned to (Mary)1/12/2004 2/9/2004 DONE
Alarm Plan Check  2/9/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/9/2004 DONE
Permit Ready to Issue  2/9/2004 DONE
Telephone call  2/9/2004 DONE
called permit ready 2-9-04 37 ///dld
Issue and Print Permit  2/9/2004 DONE
Inspection Record Card- Fire2/9/2004 2/9/2004 DONE
Plan resubmittals received  2/3/2004 DONE
Telephone call  1/26/2004 DONE
Talked to Rob at Protex, inquired why the FA system had not been expanded into the new addition. He stated that the designer was CSHQA. I said I would call them.
Telephone call  1/26/2004 DONE
Called Stephanie Cribbs at CSHQA. She stated that they wrote the specifications, but the electrical contractor was responsible for the design. The FA submittals were to be submitted to them for review prior to a city submittal. I told her that I would write a quick comment (denial) regarding the condition of the submittal and fax to ROb at Protex and a copy to her at CSHQA.
Alarm Plan Check  1/26/2004 FAIL
Resubmittal required. Faxed comments to Rob at Protex and Stephanie at CSHQA.
Application received  1/12/2004