INSP-Final Inspection | 3/24/2004 | 3/25/2004 | 3/25/2004 | A | PASS |
Rick Jackson
|
|
|
8:00
|
DOC - Permit Finaled | 3/25/2004 | 3/25/2004 | 3/25/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/25/2004 8:26:46 AM
|
INSP-Final Inspection | 3/23/2004 | 3/24/2004 | 3/24/2004 | A | DONE |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/23/2004 at 2:44:17 PM. Contact: ###-####. Per troy this was done yesterday 3/24/2004 8:02:17 AM
|
INSP-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 | P | FAIL |
Troy Cobbley
|
|
|
Door holders did not release. Contractor did not define zones 18, 19 and 20 with the monitoring company. Signals will need to be verified on these zones. Need nfpa 72 forms.
|
INSP-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 | P | FAIL |
Troy Cobbley
|
|
|
Unable to verify signals, missing smoke detector for door release. Verify induct smoke detector work was performed 3/23/2004 1:39:43 PM
|
INSP-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | FAIL |
Troy Cobbley
|
|
|
No devices tested. The remote alarm LED's for the duct smoke detectors did not operate 3/19/2004 4:06:17 PM
|
Issue and Print Permit | | | 2/17/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/13/2004 | | DONE |
|
|
|
Spoke with Rob and told him that permit is ready & fees//2/13/04 9:45am BAM
|
Plan assigned to (Mary) | 1/20/2004 | | 2/12/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/12/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/12/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/12/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/12/2004 | | 2/12/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/9/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/6/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten 2/6/2004.
|
Plan resubmittals received | | | 2/2/2004 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/29/2004 | | DONE |
|
|
|
Faxed request for matrix, completed application and clouded plans.
|
Application received | | | 1/20/2004 | | |
|
|
|
|