INSP-Final Inspection | 4/15/2004 | 4/16/2004 | 4/16/2004 | P | PASS |
Troy Cobbley
|
|
|
fire sprinklers finaled 4/16/2004 1:47:46 PM
|
DOC - Permit Finaled | 4/16/2004 | 4/16/2004 | 4/16/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 4/16/2004 1:47:51 PM
|
INSP-Final Inspection | 4/7/2004 | 4/8/2004 | 4/8/2004 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for 60 second trip test on the dry pipe system. Water made it there right on 60 seconds. Ceilings still being installed 4/8/2004 8:39:06 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/6/2004 | 4/7/2004 | 4/7/2004 | A | PASS |
Troy Cobbley
|
|
|
above ground hydro test on system additon passed 4/7/2004 2:26:15 PM
|
INSP-Conference | 4/2/2004 | 4/5/2004 | 4/5/2004 | A | PASS |
Troy Cobbley
|
|
|
Inspection was for covering of the sprinkler piping. Sprinkler piping is ok to cover. One hanger needs to be modified as discussed for piping under the duct work. 4/5/2004 11:06:00 AM
|
Plan assigned to (Bill) | 2/17/2004 | | 2/25/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/17/2004 | | 2/25/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/25/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/25/2004 | | 2/25/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/25/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/25/2004 | | DONE |
|
|
|
called jeff permit ready & fee given 2-25-04 10:52 ///dld
|
CHANGE STATUS TO (ISS) | | | 2/25/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/17/2004 | | DONE |
|
|
|
|
INSP-Conference | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | PART |
Troy Cobbley
|
|
|
inspection was for hanger attachments. attachments okay 2/12/2004 4:25:14 PM
|
INSP-Conference | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | PART |
Troy Cobbley
|
|
|
inspection was for hanger attachments. attachments okay 2/12/2004 4:25:14 PM
|
Issue and Print Permit | | | 2/3/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/20/2004 | | 2/2/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/20/2004 | | 2/2/2004 | | PART |
Bill Alexander
|
|
|
Plans are lacking. Lack detail of areas protecting, elevation changes are flip-flopping. Questioning design density (light hazard) for and F-1 occupancy, to be re-verfied with minimum construction seperation prior to acceptance, etc.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/2/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/2/2004 | | 2/2/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/2/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 1/20/2004 | | |
|
|
|
|