Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR04-00044
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameSPR HP - Environmental Chamber
Customer Number 
ePlanReview 
Description
Hewlett Packard - Building 5N * To demo 24 fire sprinklers w/lines, relocate approximately 75'-0" of 4" main, relocated drum-drip drain, install new lines and fire sprinklers on and existing 6" Reliable Model "D" dry pipe valve in the remodel of a 1920-ft/2 area of the existing north service building, converting into a new Environmental Chamber Room. This work is related to removal and installation of walls and ceilings. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-02858.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/15/20044/16/20044/16/2004PPASS
DetailsTroy Cobbley
fire sprinklers finaled 4/16/2004 1:47:46 PM
DOC - Permit Finaled4/16/20044/16/20044/16/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 4/16/2004 1:47:51 PM
INSP-Final Inspection4/7/20044/8/20044/8/2004AFAIL
DetailsTroy Cobbley
Inspection was for 60 second trip test on the dry pipe system. Water made it there right on 60 seconds. Ceilings still being installed 4/8/2004 8:39:06 AM
INSP-Sprinkler Rough-in/Hydro4/6/20044/7/20044/7/2004APASS
DetailsTroy Cobbley
above ground hydro test on system additon passed 4/7/2004 2:26:15 PM
INSP-Conference4/2/20044/5/20044/5/2004APASS
DetailsTroy Cobbley
Inspection was for covering of the sprinkler piping. Sprinkler piping is ok to cover. One hanger needs to be modified as discussed for piping under the duct work. 4/5/2004 11:06:00 AM
Plan assigned to (Bill)2/17/2004 2/25/2004 DONE
Sprinkler Plan Check2/17/2004 2/25/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/25/2004 DONE
Inspection Record Card- Fire2/25/2004 2/25/2004 DONE
Permit Ready to Issue  2/25/2004 DONE
Telephone call  2/25/2004 DONE
called jeff permit ready & fee given 2-25-04 10:52 ///dld
CHANGE STATUS TO (ISS)  2/25/2004 DONE
Plan resubmittals received  2/17/2004 DONE
INSP-Conference2/12/20042/12/20042/12/2004PPART
DetailsTroy Cobbley
inspection was for hanger attachments. attachments okay 2/12/2004 4:25:14 PM
INSP-Conference2/12/20042/12/20042/12/2004PPART
DetailsTroy Cobbley
inspection was for hanger attachments. attachments okay 2/12/2004 4:25:14 PM
Issue and Print Permit  2/3/2004 DONE
Plan assigned to (Bill)1/20/2004 2/2/2004 DONE
Sprinkler Plan Check1/20/2004 2/2/2004 PART
DetailsBill Alexander
Plans are lacking. Lack detail of areas protecting, elevation changes are flip-flopping. Questioning design density (light hazard) for and F-1 occupancy, to be re-verfied with minimum construction seperation prior to acceptance, etc.
PLANS/APPL TAKEN TO FRONT DESK  2/2/2004 DONE
Inspection Record Card- Fire2/2/2004 2/2/2004 DONE
Permit Ready to Issue  2/2/2004 DONE
Telephone call  2/2/2004 DONE
left mess that permit is ready
Application received  1/20/2004