Permit Information
Permit NumberFIR04-00060
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 391 N ANCESTOR PL
Project NameSPR MARK MONITOR-EMERAL TECH
Customer Number 
ePlanReview 
Description
(MARK MONITOR)(EMERALD TECH CENTER-BLDG F-STE 150) PARTIAL PERMIT ISSUED 2/6/04: SEE CONDITIONS OF APPROVAL INCORPROATED TO THIS PERMIT. New modify and existing shell system for the 1st time tenant improvement of 20,092-ft/2 office in existing vacant shell building space. Fire sprinkler work is related to new interior walls, new suspended ceiling system, new restrooms, and possible modifications for new mechanical and plumbing. NOTE: Prior to final IFC approval, and tenant Certificate of Occupancy being issued, the shell building permit BLD02-00699, fire permits FIR02-00273 and FIR02-00347, must be finaled and approved by inspection service signoff by the IFC Inspector. This building is fully fire sprinklered for area increase. The fire sprinkler system work shall comply with these conditions, the IFC 2000, the attached review comments, as regulated by the Fire Chief. The review notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00041.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/2/20044/2/20044/2/2004APASS
DetailsTroy Cobbley
fire sprinkler finaled
DOC - Permit Finaled4/2/20044/2/20044/2/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 4/2/2004 9:19:21 AM
INSP-Final Inspection3/16/20043/18/20043/18/2004AFAIL
DetailsTroy Cobbley
need shell system finaled. Everything else is ok 3/18/2004 9:48:55 AM
INSP-Sprinkler Rough-in/Hydro3/10/20043/11/20043/11/2004AFAIL
DetailsTroy Cobbley
Extended coverage pendants have been installed in locations shown for standard coverage pendants. Provide correct pendant or approval from Bill Alexander for change of installation. Provide additional hangers on all arm overs exceeding 24" in length per NFPA 13 9.2.3.5.1. Provide final for the shell system. This inspection was for rough-in only. 3/11/2004 10:45:29 AM
Override - Parcel Holds  2/13/2004  
Issue and Print Permit  2/13/2004 DONE
Plan assigned to (Bill)1/27/2004 2/12/2004 DONE
DetailsBill Alexander
Sprinkler Plan Check1/27/2004 2/12/2004 PASS
DetailsBill Alexander
Approved with exceptions noted in the review notes.
Miscellaneous action  2/12/2004 DONE
Emailed the following to Bob Knight, 02/12/02, 11:06am.
I don't see a "FINAL" head analysis sheet in these calcs and not all the required friction loss for piping was included for an actual spacing of 400-ft/2 between the heads on the lines and between the lines? This type of calculating is saying I can go 5 miles on 1/8 gallons of gas, but you don't figure it's all uphill.....?

I can accept this design "AS IS" for the actual spacing/design shown on the plan since you only calculated the density for a spacing of 400ft/2 without adding the required pipe friction loss of pipe to get to that spacing. You have to get there from somewhere? It just does not happen, so tell me what you want to do? "As Is" or resubmit with correction?
PLANS/APPL TAKEN TO FRONT DESK  2/12/2004 DONE
Override - Parcel Holds  2/12/2004  
Permit Ready to Issue  2/12/2004 DONE
Override - Parcel Holds  2/12/2004  
Inspection Record Card- Fire2/12/2004 2/12/2004 DONE
Telephone call  2/12/2004 DONE
Spoke with Bob and told him that permit is ready & fees//2/12/04 3:39pm BAM
Application received  1/27/2004