Permit Information
Permit NumberFIR04-00062
StatusFinaled
Name PROTEX
Site Address 2201 E PARKCENTER BLVD
Project Namealm-Gold's Gym @ Parkcenter
Customer Number 
ePlanReview 
Description
To install a required manual fire alarm system that includes sprinkler monitoring, elevator recall/shutdown and HVAC shutdown. Manual pull stations are not required if the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler flow.

The associated building permit (BLD 03-01626) is to construct a new 46,435 square foot, two story shell building and related site improvements for a future Gold's gym and exercise facility. (First Floor 31,790 sq. ft. Second Floor 14,645 sq. ft.). This building is constructed of concrete tilt-up exterior walls and glazed curtain walls with steel joists and metal pan and concrete floors and metal roof deck. This building is fully fire sprinklered. The sprinklers are used for area increase. This is a shell permit only. No occupancy is allowed under this permit. A separate tenant improvement permit is required to finish this building for occupancy. All construction per the approved plans and attached comment list. DRH03-00005/CUP02-00154/03-170/JC Gold'sGym at Parkcenter (Shell Building) -

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/1/20044/2/20044/2/2004APASS
DetailsRick Jackson
this is robs cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
DOC - Permit Finaled4/2/20044/2/20044/2/2004PPASS
DetailsRick Jackson
Finaled by inspector at 4/2/2004 4:39:55 PM
INSP-Final Inspection3/31/20044/1/20044/1/2004AFAIL
DetailsRick Jackson
This is Grants cell Have a great day!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Need approved plans 4/1/2004 12:35:09 PM
INSP-Final Inspection3/29/20043/31/20043/31/2004PCANC
DetailsRick Jackson
This is for the Tanning portion.
You can contact Rob.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
INSP-Final Inspection3/5/20043/5/20043/8/2004PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 3/5/2004 at 7:30:27 AM. Contact: ###-####. Phase I okay to occupy; will need to complete alarms in the tanning area as part of Phase II 3/8/2004 9:52:51 AM
INSP-Final Inspection3/4/20043/4/20043/4/2004PFAIL
DetailsRick Jackson
this is robs cell could we please schedule it for after 2:30 pm; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Strobes not sync'd; need to test voltage drops and current draw on NAC's 3/4/2004 5:06:05 PM
INSP-Conference2/19/20042/19/20042/19/2004PPART
DetailsRick Jackson
This is Robs Cell Phone Thanks Rick, Have a great day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley met with Rob about strobe placement at pool area and it will have to be installed at plan location or hang strobe from ceiling; elevator smoke detector to comply with state inspection as the two floor elevator has open lobbies to both floors 2/19/2004 1:59:58 PM
Issue and Print Permit  2/17/2004 DONE
Plan assigned to (Mary)1/28/2004 2/13/2004 DONE
Alarm Plan Check  2/13/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/13/2004 DONE
Permit Ready to Issue  2/13/2004 DONE
Telephone call  2/13/2004 DONE
CALLED PERMIT READY & FEE GIVEN ///DLD 2-13-04
INSP-Conference2/12/20042/12/20042/12/2004APART
DetailsRick Jackson
Site visit to check on fire alarm install - conduit being installed by ProTech; they weren't sure who was going to pull the wire 2/12/2004 10:40:18 AM
Plan resubmittals received  2/9/2004 DONE
Plan resubmittals received  2/2/2004  
Application received  1/28/2004  
Miscellaneous action  1/28/2004 DONE
Faxed request for a valid site plan. The original submittal did not include one.