INSP-Final Inspection | 7/8/2004 | 7/9/2004 | 7/9/2004 | P | PASS |
Rick Jackson
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
DOC - Permit Finaled | 7/9/2004 | 7/9/2004 | 7/9/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 7/9/2004 4:16:03 PM
|
INSP-Final Inspection | 4/6/2004 | 4/6/2004 | 4/6/2004 | P | PART |
Rick Jackson
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Phaes project and phase I is okay 4/6/2004 3:55:54 PM
|
INSP-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 | P | FAIL |
Rick Jackson
|
|
|
MARK; Phone #: ###-#### Internet Inspection Request from: Darla Downs Strobes in this area not all in this fire area (at NICU); voltage drops to 16 volts on circuit 7 4/2/2004 2:43:26 PM
|
Plan assigned to (Mary) | 1/29/2004 | | 2/24/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/24/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/24/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/24/2004 | | 2/24/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/24/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/24/2004 | | DONE |
|
|
|
spoke with Jim Shilton -- permit is ready.
|
Issue and Print Permit | | | 2/24/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/17/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/4/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jim Shilton 2/4/04.
|
Application received | | | 1/29/2004 | | |
|
|
|
|