Permit NumberFIR04-00067
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - ST LUKES 1E Morgue
Customer Number 
ePlanReview 
Description
To add smoke detectors, in-duct detectors and visual appliances to the remodeled areas. The existing required manual fire alarm system includes complete area detection, sprinkler monitoring, HVAC shutdown, elevator recall/shutdown, fire/smoke damper controls and visual and voice evac throughout.

The associated building permit (BLD 03-02540) is to remodel 4 different areas totaling 5,774 sq. ft, on the main floor for office and exam rooms per approved plans. Work includes non-combustible, non-bearing, fire-resistive construction of walls to maintain: the existing 2-hour passageway extension serving the existing 2-hour stair enclosure; construction of 1-hour fire-barrier walls at incidental use areas; creation of hospital & staff support areas; electrical, plumbing, mechanical, fire sprinkler & alarm systems alterations to meet tenant needs and provide code compliance with minimum codes. PC03-649/drs (ST LUKES-EAST TOWER-1ST FLR)(PATHOLOGY/HISTOLOGY/EMERGENCY & INTERNAL TRANSPORT)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/8/20047/9/20047/9/2004PPASS
DetailsRick Jackson
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
DOC - Permit Finaled7/9/20047/9/20047/9/2004PPASS
DetailsRick Jackson
Finaled by inspector at 7/9/2004 4:16:03 PM
INSP-Final Inspection4/6/20044/6/20044/6/2004PPART
DetailsRick Jackson
mark; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Phaes project and phase I is okay 4/6/2004 3:55:54 PM
INSP-Final Inspection4/2/20044/2/20044/2/2004PFAIL
DetailsRick Jackson
MARK; Phone #: ###-#### Internet Inspection Request from: Darla Downs Strobes in this area not all in this fire area (at NICU); voltage drops to 16 volts on circuit 7 4/2/2004 2:43:26 PM
Plan assigned to (Mary)1/29/2004 2/24/2004 DONE
Alarm Plan Check  2/24/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/24/2004 DONE
Inspection Record Card- Fire2/24/2004 2/24/2004 DONE
Permit Ready to Issue  2/24/2004 DONE
Telephone call  2/24/2004 DONE
spoke with Jim Shilton -- permit is ready.
Issue and Print Permit  2/24/2004 DONE
Plan resubmittals received  2/17/2004 DONE
Alarm Plan Check  2/4/2004 FAIL
Resubmittal required. Faxed comments to Jim Shilton 2/4/04.
Application received  1/29/2004