INSP-Final Inspection | 3/18/2004 | 3/19/2004 | 3/19/2004 | A | FAIL |
Rick Jackson
|
|
|
Warner; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes batteries not supervised; in-room detector sets off main alarms - not per plans; additional power supply not shown on plans 3/19/2004 11:02:23 AM
|
INSP-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Rick Jackson
|
|
|
Warner --- please call first; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
DOC - Permit Finaled | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/19/2004 2:16:30 PM
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 3/19/2004 | | |
|
|
|
ispection
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 3/18/2004 | | |
|
|
|
fir inspections
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/18/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/18/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
Override - Parcel Holds | | | 3/18/2004 | | |
|
|
|
|
Permit Ready to Issue | | | 3/18/2004 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 3/18/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 3/18/2004 | | 3/18/2004 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 3/18/2004 | | |
|
|
|
|
Issue and Print Permit | | | 3/18/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/15/2004 | | |
|
|
|
|
Plan assigned to (Mary) | 2/2/2004 | | 2/19/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/19/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/19/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Override - Parcel Holds | | | 2/19/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 2/19/2004 | | 2/19/2004 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 2/19/2004 | | |
|
|
|
|
Permit Ready to Issue | | | 2/19/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/19/2004 | | DONE |
|
|
|
permit ready and fees due
|
Override - Parcel Holds | | | 2/19/2004 | | |
|
|
|
|
Issue and Print Permit | | | 2/19/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/18/2004 | | DONE |
|
|
|
Spoke to Mike, I requested an updated matrix that defined the "sleeping room smoke detector" functions. He stated he would fax it over.
|
Miscellaneous action | | | 2/18/2004 | | DONE |
|
|
|
Received revised matrix from Alarmco
|
Telephone call | | | 2/10/2004 | | DONE |
|
|
|
Calling Alan Mannor in regards to the strobes connected directly to the SLC. There is no other voltage shown as connected. I don't think they function this way. Alam was out of town, Bill will call me.
|
Application received | | | 2/2/2004 | | |
|
|
|
|