Permit Information
Permit NumberFIR04-00089
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 555 S COLE RD
Project Namealm - Intermountain Gas Office
Customer Number 
ePlanReview 
Description
To replace an existing outdated FA system with a new FACP that includes non-required automatic detection, manual fire boxes, HVAC shutdown and notification throughout.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing5/5/20045/7/20045/7/2004APASS
DetailsTroy Cobbley
fire alarm finaled 5/7/2004 10:00:43 AM
DOC - Permit Finaled5/7/20045/7/20045/7/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 5/7/2004 10:00:53 AM
INSP-Alarm Testing4/29/20044/30/20044/30/2004AFAIL
DetailsTroy Cobbley
Remove all existing fire alarm equipment. Smoke detectors are overspaced in accounting (devices 23 & 24) and corridor (device 5). A/V overspaced in corridor by west stairs in basement. Install pull station (device 2) in conference center. 4/30/2004 9:09:43 AM
Miscellaneous action  3/17/2004 DONE
I requested Troy to check the door that is referenced as requiring a manual pull station per comment #3 on the review notes. Troy states that it is not utilized as an egress door and appears to look like the glass in the wall. Therefore, the manual pull station will not be required per comment #3 in the review notes.
Telephone call  3/17/2004 DONE
Spoke with Geoff Johnson, Eidam, let him know the pull station is not required per comment #3 of the review notes.
Miscellaneous action  3/16/2004 DONE
Received a letter from Eidam and Associates that state they believe the sliding door per comment #3 is not an exit and not in a common area.
Telephone call  3/16/2004 DONE
Geoff Johnson - this is a locked sliding door in a receptionist area. I stated the plans show it in a waiting area, and in an apparent common, public area as opposed to the sliding doors in each private office. I stated that I believed the manual pull station is required at that door, as it appears it could be used as an exit.
Issue and Print Permit  2/27/2004 DONE
Plan assigned to (Mary)2/10/2004 2/18/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  2/18/2004 DONE
Alarm Plan Check  2/18/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Inspection Record Card- Fire2/18/2004 2/18/2004 DONE
Permit Ready to Issue  2/18/2004 DONE
Telephone call  2/18/2004 DONE
CALLED LEFT VOISE MESSAGE FOR DAVE PERMIT READY & FEE GIVEN
Application received  2/10/2004