Permit Information
Permit NumberFIR04-00099
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Namealm - BLDG 24
Customer NumberPCS7147
ePlanReview 
Description
To install an automatic fire suppression system for a pyrophoric liquid utilizing the existing fire alarm system. 5/10/2004 - for a tool located in building 24, first floor.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  8/3/2005 DONE
Case Summary  9/21/2004 DONE
INSP-Alarm Testing5/18/20045/19/20045/19/2004PPASS
DetailsRick Jackson
Cell Ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
DOC - Permit Finaled5/19/20045/19/20045/19/2004PPASS
DetailsRick Jackson
Finaled by inspector at 5/19/2004 4:48:11 PM
INSP-Alarm Testing5/18/20045/20/20045/18/2004PCANC
DetailsRick Jackson
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino Inspection cancelled from web by: Daniel Buccino
Plan assigned to (Mary)2/12/2004 5/10/2004 DONE
Alarm Plan Check  5/10/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/10/2004 DONE
Inspection Record Card- Fire5/10/2004 5/10/2004 DONE
Permit Ready to Issue  5/10/2004 DONE
Telephone call  5/10/2004 DONE
permit ready and fee due
Issue and Print Permit  5/10/2004 DONE
Miscellaneous action  4/29/2004 DONE
E-mail:

Paul,

The previously approved alternative agent suppression systems designed and installed on specific tools utilizing TMA, pyphoric liquid may be installed on any tool utilizing phyporic liquid located in any H-5 occupancy on the Boise site. Of course, maximum allowable quantities for phyphoric liquid in the International Fire Code (IFC, 2000) are not to be exceeded.

I will be processing the current outstanding permit applications. If you have any questions, please feel free to call.


Mary


>>> 04/23/04 02:27PM >>>
Mary,
1. Alox is not TMA, it is a process utilizing TMA.

2. Per our response below on project C7147, the request and ultimate
approval of the referenced alternate was to allow Micron to operate
under the chemical quantity limits as prescribed in the 2000 edition of
the International Fire Code (IFC), as opposed to the UFC quantities in
force at the time for Micron Buildings 24 D and C. At that time, and as
a part of the request for Alternate, we did demonstrate our method of
fire suppression for a pyrophoric liquid along with many other code
required protection systems to demonstrate to the city the safeties that
would be in place. These safety systems continue to be designed and
installed per the code and do not require any alternate or agreement
that would limit their application in any H-5 area. The IFC quantity
limits are now the adopted and prescribed code limits for the city of
Boise. As such, these apply without additional requirements for an
alternative proposal and would not be restricted to any particular H-5
occupancy.

I just spoke with David Miller regarding this issue. Some alternates
that Micron has in place are building or Project specific. The
alternate that you are referencing, however, is now defunct, and I am
copying Dave at his request to make sure that we are all of the same
understanding on this issue.
Please call with any additional questions.
Thanks,
Paul


-----Original Message-----
From: Mary Froemke [mailto:MFroemke@cityofboise.org]
Sent: Thursday, April 22, 2004 2:42 PM
To: pdmarcolina
Cc: Samuel Rogers; blrice; jvelikoff
Subject: Re: FIR04-00126 C7098 - F1X Convert CVTR 148 to Alox


Paul,

Two items,

1) Is the Alox actuallly TMA?
2) Per the agreement dated May 8, 2002, only buildings 24 and 24D have
been approved. This permit is in Fab 1X. Therefore, I have a call into
Dave Miller in regards to Fab 1X.

Thanks,
Mary
Plan resubmittals received  3/12/2004 DONE
Received responses to the comments.
Alarm Plan Check  3/12/2004 FAIL
Responses are inadequate. Resubmittal is required.
Alarm Plan Check  2/27/2004 FAIL
Resubmittal required. Faxed comments to Paul Marcolina 2/27/2004.
Miscellaneous action  2/25/2004 DONE
Plans "On Hold" pending additional information from MTI regarding the chemical in use.
Application received  2/12/2004