Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00113
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3065 S BOWN WAY
Project NameSPR UG Bown Crossing Mrkt Pl
Customer Number 
ePlanReview 
Description
(Bown Crossing Market Place-Bldg F) * To install a 6" C-900 underground fire service supply main, from a service tap off Riverwalk Drive, Southeast approximately 77'-0", then South approximately 9'-0" into the Northeast corner of the building, and up through the floor with 6" Ductile Iron, to approximately 6" above the floor. This building will be a 6,925-ft/2 two story, multi-tenant, residential and mercantile shell building. Separate permits and plans must be obtained and approved for the overhead shell and each tenant space to be occupied. This building is sprinklered for occupancy separation reduction and fire flow requirements. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 and the IFC-2002, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-02291.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Supply line flush7/19/20047/20/20047/20/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/19/2004 at 12:58:54 PM. UG completed 7/20/2004 1:22:20 PM
DOC - Permit Finaled7/20/20047/20/20047/20/2004PPASS
DetailsRick Jackson
Finaled by inspector at 7/20/2004 1:22:32 PM
INSP-Sprinkler Rough-in/Hydro5/13/20045/13/20045/13/2004PPASS
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Hydro only okay 5/13/2004 2:31:00 PM
INSP-Sprinkler Rough-in4/22/20044/23/20044/23/2004APART
DetailsRick Jackson
underground supply line rough in inspection please////sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore okay to cover 4/23/2004 2:30:39 PM
Plan assigned to (Bill)2/17/2004 2/19/2004 DONE
Sprinkler Plan Check2/17/2004 2/19/2004 PASS
DetailsBill Alexander
This is a faxed permit and relates to the underground fire service supply only.
PLANS/APPL TAKEN TO FRONT DESK  2/19/2004 DONE
Permit Ready to Issue  2/19/2004 DONE
Inspection Record Card- Fire2/19/2004 2/19/2004 DONE
Telephone call  2/19/2004 DONE
Spoke with Jeff Anderson and told him that permit is ready & fees//2/19/04 2:12pm BAM
Issue and Print Permit  2/19/2004 DONE
Application received  2/17/2004