Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR04-00123
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 631 S 9TH ST
Project NameSPR IDAHO SELF STORAGE "C"
Customer Number 
ePlanReview 
Description
(IDAHO SELF STORAGE)(BUILDING "C") * To install a new fire sprinkler system in an existing 11,628-ft/2 type V-B nonrated warehouse structure that will used for misc. storage. Limits of storage are: Class I through III, palletized, in bin boxes, shelf or rack do not exceed 12'-0". Class IV in palletized, in bin boxes or shelf (no rack) cannot exceed 10'-0". Group "A" plastics in approved racks, solid pile, palletized, bin boxes or shelf storage cannot exceed 5'-0", with exceptions (reference NFPA 13:12.1.10.1.1). Miscellaneous tire storage on floor, on tread or on side, in single or double or multirow approved racks on tread or flat cannot exceed 5'-0", with exception (reference NFPA 13:12.1.10.1.1). The building will have non-bearing interior panel walls to create storage units with open ceilings. New lighting and HVAC are also being installed which may affect fire sprinkler protection coverage. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-02195.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/30/20044/30/20044/30/2004PPASS
DetailsRick Jackson
DOC - Permit Finaled4/30/20044/30/20044/30/2004PPASS
DetailsRick Jackson
Finaled by inspector at 4/30/2004 3:40:18 PM
INSP-Conference4/14/20044/14/20044/14/2004PPART
DetailsRick Jackson
devin; Phone #: ###-#### Internet Inspection Request from: Darla Downs See BLD permit; about knox box location with GC 4/14/2004 2:37:31 PM
INSP-Sprinkler Rough-in/Hydro4/8/20044/9/20044/9/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/8/2004 at 5:32:30 PM. Overhead hydro okay 4/9/2004 12:52:56 PM
INSP-Sprinkler Rough-in/Hydro4/6/20044/8/20044/8/2004PPART
DetailsTroy Cobbley
Underground hydro test is ok and the sprinkler rough-in is ok. Above ground hydro test failed. It appears the gauge fitting might be leaking 4/8/2004 3:28:43 PM
INSP-Supply line flush3/12/20043/12/20043/12/2004PCANC
DetailsTroy Cobbley
Wrong permit number called in. See fir03-00668 3/12/2004 1:43:55 PM
Plan assigned to (Bill)2/18/2004 2/27/2004 DONE
Sprinkler Plan Check2/18/2004 2/27/2004 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/27/2004 DONE
Inspection Record Card- Fire2/27/2004 2/27/2004 DONE
Permit Ready to Issue  2/27/2004 DONE
Telephone call  2/27/2004 DONE
called Greg permit ready & fee given 2-27-04 8:46 ///dld
Issue and Print Permit  2/27/2004 DONE
Application received  2/18/2004