Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR04-00132
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 100 E IDAHO ST
Project NameSPR ST. LUKES - MISTI
Customer Number 
ePlanReview 
Description
ST. LUKES REGIONAL MEDICAL CENTER - MSTI * To change out some existing 4" supply main piped which was connected improperly (should have been 6"), off the existing wet system, located on a pump system located in Pump Room B-76 located in the basement, near the elevators. To modify and existing 6" FDC/Standpipe supply main to create a combination FDC/Standpipe supply and Fire Pump Test piping. This includes adding a supervised (normally open) 6" control valve in the existing 6" Fire Department Connection (at the basement mechanical room I-276), and another 4" supervised (normally closed) valve in the new 4" tap test line to be piped out into a new 2.5 x 2.4 pump test header, located through the outside next to existing North side of the facility. This work is required per NFPA 20:5.19.1.1 and FM (underwriter) request. All fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro7/15/20047/21/20047/21/2004APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/15/2004 at 3:27:55 PM. Contact: ###-####.
INSP-Final Inspection7/19/20047/21/20047/21/2004APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/19/2004 at 5:22:49 PM. Contact: ###-####.
DOC - Permit Finaled7/21/20047/21/20047/21/2004APASS
DetailsRick Jackson
Finaled by inspector at 7/21/2004 10:40:38 AM
INSP-Final Inspection5/12/20045/13/20045/13/2004PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/12/2004 at 8:19:49 AM. Butterfly valve requires monitoring by fire alarm system 5/13/2004 2:28:40 PM
Issue permit  3/3/2004 DONE
Plan assigned to (Bill)2/23/2004 3/2/2004 DONE
Sprinkler Plan Check2/23/2004 3/2/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  3/2/2004 DONE
Inspection Record Card- Fire3/2/2004 3/2/2004 DONE
Permit Ready to Issue  3/2/2004 DONE
Telephone call  3/2/2004 DONE
permit ready and fees due
Application received  2/23/2004