Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00143
StatusFinaled
Name MOUNTAIN ALARM
Site Address 4860 W EMERALD ST
Project Namealm - Emerald Lanes
Customer Number 
ePlanReview 
Description
To replace an existing sprinkler monitoring system that includes HVAC shutdown and monitoring for a cooking hood. The existing system is non-code compliant.

There is no associated building permit.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing12/7/200412/8/200412/8/2004APASS
DetailsTroy Cobbley
fire alarm finaled 12/8/2004 2:49:23 PM
DOC - Permit Finaled12/8/200412/8/200412/8/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 12/8/2004 2:49:33 PM
INSP-Final Inspection11/19/200411/19/200411/19/2004PFAIL
DetailsTroy Cobbley
Need to test hood and duct detectors to final 11/19/2004 3:07:45 PM
INSP-Final Inspection11/17/200411/18/200411/18/2004PCANC
DetailsTroy Cobbley
Linda; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner
INSP-Sprinkler Rough-in/Hydro11/18/200411/18/200411/18/2004PCANC
DetailsTroy Cobbley
duplicate inspection. Rescheduled for tomorrow 11/18/2004 4:01:02 PM
FIR-Aging Inspection6/15/20046/15/20046/15/2004 NR
DetailsTroy Cobbley
Installation is nearly complete. Alarm contractor is searching for a tamper switch for a sprinkler valve. 6/15/2004 11:31:35 AM
Permit Ready to Issue  3/16/2004  
Inspection Record Card- Fire3/16/2004 3/16/2004 DONE
Telephone call  3/16/2004 DONE
left mess that permit is ready
Issue and Print Permit  3/16/2004 DONE
Plan assigned to (Mary)2/26/2004 3/15/2004 DONE
Alarm Plan Check  3/15/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Plan resubmittals received  3/15/2004 DONE
Received required cut sheets via fax.
PLANS/APPL TAKEN TO FRONT DESK  3/15/2004 DONE
Alarm Plan Check  3/12/2004 FAIL
Resubmittal required. Faxed comments to Robert Bailey 3/12/2004.
Telephone call  3/9/2004 DONE
Request to Robert Bailey to fax over manufacturer's cut sheets that show the FACP battery charging capacity and maximum battery size. Also need battery cut sheets.
Application received  2/26/2004