Permit NumberFIR04-00151
StatusFinaled
Name SYSTEM SERVICES, LLC
Site Address 111 S AUTO DR
Project Namealm - CALVARY CHAPEL
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system in the building. HVAC shutdown and sprinkler monitoring shall be connected to the FAS.

The associated building permit (BLD 03-02402) is to convert an existing 2 story, 6,584 square foot building to an elementary school. The 1st floor has a floor area of 3,340 square feet (101 occupant load) and the 2nd floor has a floor area of 3,244 square feet (96 occupant load). Work is to include interior nonbearing walls, new exterior doors, two reconstructed stairways, and a wheelchair lift all per the approved drawings and the plan review report on file. The fire sprinkler system shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW** CUP03-00063 and DRH03-00134. (CALVARY CHAPEL - ELEMENTARY SCHOOL BUILDING) This building is fire sprinklered for story increase and to allow both 2nd floor stairways to be open.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  8/25/2004 DONE
INSP-Final Inspection4/22/20044/23/20044/23/2004APASS
DetailsTroy Cobbley
fire alarm finaled 4/23/2004 10:21:43 AM
DOC - Permit Finaled4/23/20044/23/20044/23/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 4/23/2004 10:21:48 AM
INSP-Final Inspection4/21/20044/21/20044/21/2004PFAIL
DetailsTroy Cobbley
mount map, shut down all hvac units upon activation of a duct smoke detector, monitoring company did not receive all of the signals and what they did receive was not right, (all devices need retested), verify a/v locations, mount knox box and provide signage on riser room door. Get nfpa 72 forms 4/21/2004 4:34:05 PM
INSP-Conference4/1/20044/2/20044/2/2004ADONE
DetailsTroy Cobbley
contractor wanted to discuss location of smoke detector over the facp and strobe locations 4/2/2004 1:00:34 PM
Issue and Print Permit  3/29/2004 DONE
Inspection Record Card- Fire3/22/2004 3/22/2004 DONE
Permit Ready to Issue  3/22/2004 DONE
Telephone call  3/22/2004 DONE
permit ready and fee due
Plan resubmittals received  3/19/2004  
Alarm Plan Check  3/19/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/19/2004 DONE
Plan assigned to (Mary)3/4/2004 3/19/2004 DONE
Plan resubmittals received  3/17/2004  
Plan resubmittals received  3/17/2004  
INSP-Conference3/8/20043/8/20043/8/2004ADONE
DetailsTroy Cobbley
I stopped at the job site and posted a stop work order against the fire alarm system. The fire alarm panel and conduit have been installed by Idaho Electric. The installers name is Neil Lake. I spoke to Brad, who is the owner of Idaho Electric, about not installing without approved plans. I also spoke to Patrick with system services who actually submitted the plans.
INSP-Conference3/5/20043/5/20043/5/2004PDONE
DetailsTroy Cobbley
I stopped at the project to do an underground inspection and saw the fire alarm panel mounted in the entry lobby of the building. I sent an e-mail to Mary
INSP-Conference3/5/20043/5/20043/5/2004PDONE
DetailsTroy Cobbley
I stopped at the project to do an underground inspection and saw the fire alarm panel mounted in the entry lobby of the building. I sent an e-mail to Mary
Application received  3/4/2004  
Alarm Plan Check3/10/2004   FAIL
Resubmittal required. Faxed comments to Patrick Gill 3/10/2004.