Permit Information
Permit NumberFIR04-00155
StatusFinaled
Name ALLIED GENERAL
Site Address 200 N 6TH ST
Project Namealm -CENTRAL FIRE STATION
Customer Number 
ePlanReview 
Description
To provide a new fire sprinkler monitoring system. This system includes the monitoring of a dry pipe sprinkler valve and eight duct smoke detectors.
The associated building permit (BLD 04-00031) is to create a 4,670 square foot restaurant on the first floor of an existing 2-story building. This project is a change of occupancy. The first floor has a total floor area of 4,900 square feet. Operations that produce grease-laden vapors and/or produce smoke are not allowed within this tenant space except for limited operations as approved by the Fire Department. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, finishes, booths, an exterior landing at the North door, and a bar all per the approved drawings and the plan review report on file. This building is required to be fire sprinklered to allow an A-2 Occupancy, to allow the unprotected openings in the East wall, to allow the basement to be unenclosed, and for story increase. The fire sprinkler system shall comply with NFPA 13-2002 as regulated by the Fire Department.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/28/20045/28/20045/28/2004PPASS
DetailsRick Jackson
DOC - Permit Finaled5/28/20045/28/20045/28/2004PPASS
DetailsRick Jackson
Finaled by inspector at 5/28/2004 5:00:07 PM
INSP-Alarm Testing5/24/20045/25/20045/25/2004PFAIL
DetailsTroy Cobbley
Fire alarm was not ready due to missing makeup air unit and two thermoustats not wired and high and low voltage wire in the same conduit at dry pipe pressure switch. Sprinklers could not be finaled due to missing ceiling tile and canopies. Contractor needs to review fire dept. review notes prior to calling for inspection (fire extinguishers not ready nor was door hardware). All previous correction notices need to be verified for compliance. 5/25/2004 2:51:01 PM
INSP-Alarm Testing5/20/20045/24/20045/24/2004AFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Cliff Miller outside sprinkler bell not working with dry flow; change descriptors to indicate dry and wet sprinkler flow zones; need maps; need to test all duct detectors; need record of completion 5/24/2004 4:33:47 PM
Inspection Record Card- Fire3/22/2004 3/22/2004 DONE
Permit Ready to Issue  3/22/2004 DONE
Telephone call  3/22/2004 DONE
permit ready and fee due
Issue and Print Permit  3/22/2004 DONE
Alarm Plan Check3/19/2004 3/19/2004 PASS
PLANS/APPL TAKEN TO FRONT DESK  3/19/2004 DONE
Inspection Record Card- Fire3/19/2004 3/19/2004 DONE
Permit Ready to Issue  3/19/2004 DONE
Application received  3/5/2004  
Plan assigned to (SAM)3/5/2004