Permit Information
Permit NumberFIR04-00158
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 4696 W OVERLAND RD
Project NameSPR HILCREST B.P. 2ND FLOOR
Customer Number 
ePlanReview 
Description
(PATRICK MCKEEGAN ARCHITECTS)(HILLCREST BUSINESS CENTER-2ND FLR) To remodel an 836-ft/2 office located on the second floor per approved plans. Fire sprinkler work is related to new partitions. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00099.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/22/20043/23/20043/23/2004APASS
DetailsTroy Cobbley
fire sprinklers finaled 3/23/2004 9:51:30 AM
DOC - Permit Finaled3/23/20043/23/20043/23/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 3/23/2004 9:51:34 AM
INSP-Final Inspection3/18/20043/19/20043/18/2004ACANC
DetailsTroy Cobbley
smick- ###-#### Disp set to [CANC] by a contractor via Hello! on Mar 18 2004 3:17PM.
Issue permit  3/18/2004  
Plan assigned to (Bill)3/8/2004 3/9/2004 DONE
Sprinkler Plan Check3/8/2004 3/9/2004 FAIL
DetailsBill Alexander
Faxed permit.
a. Piping installed is different than plan provided. Provide corrected drawing incorporating correct piping meeting the minimum allowed spacing approved. If this floor or any other floor (incorporating the same system was installed differently than approved plans on file, then this and all other related fire protection work is declared deficient and this facility shall require reverification with calculations and corrected plans that correlate. (IFC 105.2.1, 105.4.2, 901.2)

b. It is also apparent that the floor layout is different than the original Designer plan show a storage room? Architectural plans address this room as a break room? Occupancy hazard difference applies to each. Provide information dealing with the actual occupancy use and resubmit. If OH occupancy applies, provide protection and construction clarification on the plans that meet the occupancy use. (IFC 105.2.1, 105.4.2, 901.2)

c. The ceiling is shown to be 7'-10" elevation. Designers "Pony" walls are 6'-4" which shall be verified. Any distance less than 18" between the floor mounted obstruction and the deflector must apply with NFPA 13:8.6.5.2. (IFC 105.2.1, 105.4.2, 901.2)
Miscellaneous action  3/9/2004 DONE
Faxed copy of faile review to Simplex Grinnell (8:35 am)
Plan resubmittals received  3/9/2004  
Sprinkler Plan Check3/9/2004 3/9/2004 PASS
DetailsBill Alexander
Faxed permit.
PLANS/APPL TAKEN TO FRONT DESK  3/9/2004 DONE
Inspection Record Card- Fire3/9/2004 3/9/2004 DONE
Permit Ready to Issue  3/9/2004 DONE
Telephone call  3/9/2004 DONE
spoke with Tom -- permit is ready.
Application received  3/8/2004