Permit Information
Permit NumberFIR04-00161
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3033 W ELDER ST
Project NameSPR WELLS FARGO
Customer Number 
ePlanReview 
Description
(WELLS FARGO SERVICE CENTER)(MECHANICAL UPGRADE) BUILDING #1 - To install a new auxiliary Pre-Action fire suppression system in the Data (Computer) Room/s and above its combustible cavity ceilings previously protected with Halon suppression agent systems. The underfloor combustible areas will be protected with an extended existing wet system. This building is fully fire sprinklered for area increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-03054.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  8/28/2008 DONE
INSP-Final Inspection6/1/20056/7/20056/7/2005PPASS
DetailsForrest France
Fire sprinkler finaled.
Inspection Record Card- Fire6/1/2005 6/1/2005 DONE
Permit Ready to Issue  6/1/2005 DONE
Telephone call  6/1/2005 DONE
talked to receptionist ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  6/1/2005 DONE
Sprinkler Plan Check5/26/2005 5/31/2005 PASS
5/26/2005, 11:30am. Floor plan changed greatly and lack verification of meeting minimum requirements for hte design.

5/31/2005, Received modified plan with revised calculations for verification of the revision.
Plan assigned to (Bill)5/26/2005 5/31/2005 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/31/2005 DONE
INSP-Final Inspection5/25/20055/31/20055/27/2005PCANC
DetailsTroy Cobbley
kerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Inspection cancelled from web by: Marsha Smylie
Miscellaneous action  5/26/2005 DONE
Received a faxed area floor plan change modification from Tom Easton, which was returned with code questions.
Plan resubmittals received  5/26/2005  
Faxed
INSP-Final Inspection5/13/20055/16/20055/16/2005PFAIL
DetailsForrest France
Two upright heads in vault are spaced too far off wall to meet OH 1 requirements for this space. Provide map at riser indicating location of auxillary drains. Provide test certificates. Verify foreward flow through BFP as required by note #59. Provide sp
INSP-Sprinkler Rough-in/Hydro2/2/20052/2/20052/2/2005APART
DetailsRick Jackson
Air test okay; need to add EQ at new main; different heads used in underfloor area; need as-builts for addition to under floor in phone room 2/2/2005 9:45:34 AM
INSP-Sprinkler Rough-in/Hydro1/31/20052/1/20052/1/2005APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/31/2005 at 6:43:05 PM. Contact: ###-####. Start air test at 43 psi 2/1/2005 11:17:05 AM
INSP-Sprinkler Rough-in/Hydro1/28/20051/31/20051/31/2005PPART
DetailsRick Jackson
Mick; Phone #: ###-#### Internet Inspection Request from: Jan Rice hydro okay 1/31/2005 4:03:52 PM
FIR-Aging Inspection12/27/200412/27/200412/28/2004 PASS
DetailsRick Jackson
Talked to Roger and the work is in process and the final should be called in very soon 12/28/2004 9:30:19 AM
Miscellaneous action  11/4/2004 DONE
Removed this permit from BLD03-03054 since after field verification by Rick Jackson, it has no related connection.
Issue and Print Permit  9/27/2004 DONE
Permit Ready to Issue  9/24/2004 DONE
Inspection Record Card- Fire9/24/2004 9/24/2004 DONE
Telephone call  9/24/2004 DONE
Left message for Tom and told him that permit is ready & fees///9/24/04 11:40am BAS
Sprinkler Plan Check9/8/2004 9/23/2004 DONE
DetailsBill Alexander
Received call from Tom Easton 9/15/04 requesting the 2nd submittal be tossed and replace with 9/20/04. Reference (sent email 09/14/04) regarding beams identified in O.H. cavity which affect upright spacing/coverage.

09/23/04 approved as submitted and per attached REV comments
Plan assigned to (Bill)9/8/2004 9/23/2004 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  9/23/2004 DONE
Plan resubmittals received  9/20/2004 DONE
Plan resubmittals received  9/8/2004  
Issue permit  7/26/2004 DONE
Miscellaneous action  7/15/2004 DONE
Emailed Tom Easton on why he has not picked up plans. Response is: Wells Fargo is considering a change to the below floor sprinkler system to make it wet instead of pre-action to hold down their alarm costs. I should know if I have to change my design by next week. We have not picked the plans up because I'm sure we will owe more than the current permit fee.
Sprinkler Plan Check6/16/2004 6/21/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/21/2004 DONE
Inspection Record Card- Fire6/21/2004 6/21/2004 DONE
Permit Ready to Issue  6/21/2004 DONE
Telephone call  6/21/2004 DONE
PERMIT READY AND FEE DUE
Plan assigned to (Bill)3/8/2004 6/21/2004 DONE
Plan resubmittals received  6/16/2004  
Sprinkler Plan Check6/3/2004 6/14/2004 FAIL
DetailsBill Alexander
1. Need backflow prevention per Idaho State Drinking Water Regulation, Title 1, Chapter 8, Section 16.01.8601.04 Article A. w/forward flow appurtenance.
2. Need Revised calcs with backflow incorporated for this and existing systems.
3. Need elevation dimensioning of existing and new 6" and 4" mains.
4. Need locations, ways, means and signage to all trapped piping drains for preaction system.
5. Need data submittals of system air maintenance device.
6. Need information of hangers added for mains and lines which will incorporate trapeze hangers which required engineering and identified on the plans.
7. Sidewall on Preaction systems only allowed if piping is not trapped.

Miscellaneous action  6/14/2004 DONE
Took failed documents to "permit desk" for calling and returning.
Telephone call  6/14/2004 DONE
plans failed called tom easton to return
Plan resubmittals received  6/3/2004 DONE
Sprinkler Plan Check3/8/2004 3/11/2004 FAIL
DetailsBill Alexander
Wrong building permit. Many design code issues that are to numerous to include here. See attached letter response.
Miscellaneous action  3/11/2004 DONE
Took failed plans to the front desk for calling and returning. Faxed copy of failed letter to Tom Easton, Simplex/Grinnell.
Telephone call  3/11/2004 DONE
Permit denied
Application received  3/8/2004