INSP-Final Inspection | 6/25/2004 | 6/25/2004 | 6/25/2004 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 6/25/2004 | 6/25/2004 | 6/25/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/25/2004 9:54:41 AM
|
INSP-Alarm Testing | 6/23/2004 | 6/24/2004 | 6/24/2004 | A | FAIL |
Troy Cobbley
|
|
|
Repair horns in rooms 201 and 104. Repair flow switch. Provide signage on door to riser and facp. 6/24/2004 2:51:33 PM
|
INSP-Alarm Testing | 6/22/2004 | 6/23/2004 | 6/23/2004 | P | CANC |
Troy Cobbley
|
|
|
Cancelled by contractor. 6/23/2004 4:25:51 PM
|
Issue permit | | | 6/18/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/14/2004 | | 6/14/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/14/2004 | | DONE |
|
|
|
|
Telephone call | | | 6/14/2004 | | DONE |
|
|
|
permit ready and fee due
|
Alarm Plan Check | | | 6/11/2004 | | PASS |
|
|
|
Plan Modifications. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/11/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/8/2004 | | |
|
|
|
|
INSP-Final Inspection | 5/27/2004 | 5/27/2004 | 5/27/2004 | P | FAIL |
Troy Cobbley
|
|
|
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
|
Issue and Print Permit | | | 4/13/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 3/9/2004 | | 4/9/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/9/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/9/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/9/2004 | | 4/9/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/9/2004 | | DONE |
|
|
|
|
Telephone call | | | 4/9/2004 | | DONE |
|
|
|
left a message for John permit is ready.
|
Telephone call | | | 4/7/2004 | | DONE |
|
|
|
Called to let John know that the single station smoke detectors were not included on the last set of plans. He will send someone down to transfer from set #2 to set #3.
|
Telephone call | | | 3/25/2004 | | DONE |
|
|
|
John Lopez, I explained the exits were corridors and I would expect A/V within 15' of each end. I stated I would accept new calcs, riser and plans and include them as his 2nd submittal.
|
Plan resubmittals received | | | 3/23/2004 | | |
|
|
|
|
Alarm Plan Check | | | 3/15/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to John Lopez 3/15/2004.
|
Application received | | | 3/9/2004 | | |
|
|
|
|