Permit Information
Permit NumberFIR04-00162
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 3323 N LAKEHARBOR LN
Project NameSILVER LAKE APARTMENTS
Customer Number 
ePlanReview 
Description
A required manual and automatic fire alarm system is required for all group R-1 occupancies. (UFC 1007.2.9) The fire alarm system will include sprinkler monitoring.

The associated building permit (BLD 02-01157) is to construct a new 16,416 sq.ft. three story, wood framed, 18 unit apartment building. The first floor is 7,506 sq.ft. and the second floor is 7,080 sq.ft. and the third floor is 1,830 sq.ft. NOTE: This building is fire sprinklered per NFPA 13-R. All construction per the approved plans and attached comment list. PC #310-02 DRH01-00233 SS CUP01-00159 DAA (Building B)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/25/20046/25/20046/25/2004APASS
DetailsRick Jackson
DOC - Permit Finaled6/25/20046/25/20046/25/2004APASS
DetailsRick Jackson
Finaled by inspector at 6/25/2004 9:54:41 AM
INSP-Alarm Testing6/23/20046/24/20046/24/2004AFAIL
DetailsTroy Cobbley
Repair horns in rooms 201 and 104. Repair flow switch. Provide signage on door to riser and facp. 6/24/2004 2:51:33 PM
INSP-Alarm Testing6/22/20046/23/20046/23/2004PCANC
DetailsTroy Cobbley
Cancelled by contractor. 6/23/2004 4:25:51 PM
Issue permit  6/18/2004 DONE
Inspection Record Card- Fire6/14/2004 6/14/2004 DONE
Permit Ready to Issue  6/14/2004 DONE
Telephone call  6/14/2004 DONE
permit ready and fee due
Alarm Plan Check  6/11/2004 PASS
Plan Modifications. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  6/11/2004 DONE
Plan resubmittals received  6/8/2004  
INSP-Final Inspection5/27/20045/27/20045/27/2004PFAIL
DetailsTroy Cobbley
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
Issue and Print Permit  4/13/2004 DONE
Plan assigned to (Mary)3/9/2004 4/9/2004 DONE
Alarm Plan Check  4/9/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/9/2004 DONE
Inspection Record Card- Fire4/9/2004 4/9/2004 DONE
Permit Ready to Issue  4/9/2004 DONE
Telephone call  4/9/2004 DONE
left a message for John permit is ready.
Telephone call  4/7/2004 DONE
Called to let John know that the single station smoke detectors were not included on the last set of plans. He will send someone down to transfer from set #2 to set #3.
Telephone call  3/25/2004 DONE
John Lopez, I explained the exits were corridors and I would expect A/V within 15' of each end. I stated I would accept new calcs, riser and plans and include them as his 2nd submittal.
Plan resubmittals received  3/23/2004  
Alarm Plan Check  3/15/2004 FAIL
Resubmittal required. Faxed comments to John Lopez 3/15/2004.
Application received  3/9/2004