INSP-Alarm Testing | 4/30/2004 | 4/30/2004 | 4/30/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled 4/30/2004 2:48:13 PM
|
DOC - Permit Finaled | 4/30/2004 | 4/30/2004 | 4/30/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 4/30/2004 2:48:18 PM
|
Alarm Plan Check | | | 4/29/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/29/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/29/2004 | | 4/29/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/29/2004 | | DONE |
|
|
|
|
Telephone call | | | 4/29/2004 | | DONE |
|
|
|
permit ready and fee due
|
Issue permit | | | 4/29/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 4/22/2004 | 4/23/2004 | 4/23/2004 | P | CANC |
Troy Cobbley
|
|
|
cancelled by Jason Minnic with AEI until resubmittals are approved 4/23/2004 2:27:35 PM
|
Plan resubmittals received | | | 4/23/2004 | | |
|
|
|
|
Plan assigned to (Mary) | 3/15/2004 | | 4/19/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/19/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/19/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/19/2004 | | 4/19/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/19/2004 | | DONE |
|
|
|
|
Telephone call | | | 4/19/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 4/19/2004 | | |
|
|
|
|
Telephone call | | | 4/14/2004 | | DONE |
|
|
|
Jason Minnick, six (6) fire/smoke dampers on the second floor have been deleted. They just resubmitted yesterday (the resubmittal shows the dampers). I stated I would review what he gave me, we'll get the permit issued so they can start work, and they will need to resubmit plan modifications prior to final inspection.
|
Plan resubmittals received | | | 4/13/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/30/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jason Minnick 3/30/2004.
|
Telephone call | | | 3/30/2004 | | DONE |
|
|
|
Heads up to Jason Minnick that the building comments #13 have access-controlled egress doors listed. He stated he was aware of it (we discussed it previously) and will include it on his resumbittal.
|
Telephone call | | | 3/19/2004 | | DONE |
|
|
|
Jason Minnick (AEI) I requested more information regarding the security access controlled egress doors (the riser shows no means of disabling the doors upon FA alarm). The notification appliances on the second floor are sporatically placed. I will need to review the building's history and AEI may need to either remove them or provide throughout the space. I told Jason I would contact him on Monday and let him know about the notificaiton appliances and he could let me know if the panel has the security release as an existing item.
|
Application received | | | 3/15/2004 | | |
|
|
|
|